Multiple dryer (common) venting – Maytag MDG120 User Manual
Page 12
Attention! The text in this document has been recognized automatically. To view the original document, you can use the "Original mode".
IMPORTANT:
For extended duct work runs, the
cross section area of the duct work can only be
increased to an extent. Maximum proportional
duct work runs
cannot
exceed twenty (20) feet
more than the original limitations of twenty (20)
feet with two (2) elbows. When the duct work
approaches the maximum limits as noted in this
manual, a professional heating venting air
conditioning
(HVAC)
firm
should be
consulted
for proper venting information.
IMPORTANT; DO NOT
use screens, louvers, or
caps on the outside of opening of exhaust duct
work
MULTIPLE DRYER (COMMON)
VENTING
If it is not feasible to provide separate exhaust
ducts for each dryer, ducts from individual
dryers may be channeled into a “common main
duct.” The individual ducts should enter the
bottom or side of the main duct at an angle not
more than 45° in the direction of air flow and
should be
spaced at least
48-%
inches apart.
The main duct
should be
tapered, with the
diameter increasing before each individual 14-
inch (minimum) duct is added.
IMPORTANT:
The MDG120 is not provided with
a back draft damper. When exhausted into a
multiple (common) exhaust line, a back draft
damper
must be
installed at each dryer duct.
IMPORTANT:
No more than four (4) dryers
should be
connected to one main common
duct.
The main duct may be any shape or cross sec
tional area, so long as the minimum cross section
area is provided. See the
illustrations
showing
the minimum cross section area for multiple dryer
round or square venting. These figures
must be
increased 10 square inches when rectangular
main ducting is used, and the ratio of duct width
to depth should not be greater than
3
-V
2
to 1.
These figures
must be
increased in proportion if
the main duct run to the last dryer to where it
exhausts to the outdoors is unusually long (over
20
feet) or has numerous elbows (more than two
[2]) in it. In calculating duct work size, the cross
section area of a square or rectangular duct
must
be
increased
20
percent for each additional
20
feet. The diameter of a round exhaust must be
increased
10
percent for each additional
20
feet.
Each 90° elbow is equivalent to an additional 30
feet and each 45° elbow is equivalent to an
additional 15 feet.
MULTIPLE DRYER VENTING WITH
14” DIAMETER (2,150 CFM) EX
HAUST CONNECTIONS AT COM
MON DUCT
VtRTlCAL OUCTHa
NO. OF ORrSRS
i
1
HKlijHThoss
«5
380 299 119
ÄMHüH WÍW ■
DUCT DIAMETCR 2< 22 te U MOWIZOKTAU OUCTWO Д18-Д.-V - _l 2X0 aSARANCE MQN--------- r I-<9 3/8’ 2X0 CLEARANCE IMPORTANT: NO MORE THAN 4 DRYERS CAN BE CONNECTED TO ONE COMMON DUCT (VENT). FORMULAS TO CALCULATE DUCTING CROSS SECTIONAL AREA CROSS SECTIONAL AREA OF A ROUND DUCT = .785 X D2 WHERE D = DIAMETER OF THE DUCT o CROSS SECTIONAL AREA OF A RECTANGULAR DUCT = WXH WHERE W= WIDTH AND H = HEIGHT I NOTE A: OPENING MUST BE TWO (2) INCHES LARGER THAN DUCT (ALL THE WAY AROUND) THE DUCT MUST BE CENTERED WITHIN THIS OPENING IMPORTANT: For extended duct work runs, the cross section area of the duct work can only be duct work runs cannot exceed twenty (20) feet more than the original limitations of twenty (20) feet with two (2) elbows. When the duct work manual, a professional HVAC firm should be IMPORTANT: Exhaust back pressure measured by a manometer at each dryer should not exceed 0.3 inches of water column. 12
increased to an extent. Maximum proportional
approaches the maximum limits as noted in this
consulted for proper venting information.
exhaust duct area