beautypg.com

Outside ductwork protection, Single dryer venting – Maytag MDG120 User Manual

Page 11

Attention! The text in this document has been recognized automatically. To view the original document, you can use the "Original mode".

background image

bustible materials, the opening must be 2
inches larger (all the way around) than the duct.

The duct

must be

centered within this opening.

OUTSIDE DUCTWORK
PROTECTION

To protect the outside end of horizontal duct
work from the weather, a 90° elbow bent down­
ward

should be

installed where the exhaust

VERTICAL DUCTING

exits the building. If the exhaust duct work
travels vertically up through the roof, it should
be protected from the weather by using a 180°
turn to point the opening downward. In either
case, allow at least twice the diameter of the

duct between the duct opening and the nearest
obstruction.

IMPORTANT: DO NOT use screens or caps on
the outside of opening of exhaust duct work.

NOTE “A” - Opening must be two (2) inches larger than duct (all the way around). The duct must be

centered within this opening.

SINGLE DRYER VENTING

Where possible. It is suggested to provide a
separate exhaust duct for each dryer. The
exhaust duct

should be

laid out in such a way

that the duct work travels as directly as possible
to the outdoors with as few turns as possible. It

is suggested that the use of 90° turns in ducting
be avoided: use 30° and/or 45° angles instead.
The shape of the exhaust duct work is not
critical so long as the minimum cross section

area is provided.

Minimum duct size for a gas dryer is 14-inches

for a round duct or 12.50” x 12.50” for a square

duct. Duct size

must not

be reduced anywhere

down stream of dryer.

HORIZONTAL DUCTING

It is suggested that the duct work from each

dryer (minimum 14 inches) not exceed 20 feet
with no more than two (2) elbows (excluding
dryer connections). If the duct work exceeds 20
feet or has numerous elbows, the cross section
area of the duct work

must be

increased in

proportion to the length and number of elbows
in it. In calculating duct size, the cross section
area of a square or rectangular duct

must be

increased by 20 percent for each additional 20

feet. The diameter of a round exhaust duct

should be

increased

10

percent for each

additional 15 feet. Each 90° elbow is equivalent
to an additional 30 feet, and each 45° elbow is
equivalent to an additional 15 feet.

VERTICAL DUCTING

SIDE VIEW OF DRYER

(SECTION VIEW)

NOTE "A” - Opening must be two (2) inches larger than duct (all the way around). The duct must be

centered within this opening.

NOTE "B” - Inspection doors should be installed at strategic points for periodic inspection and cleaning.

11