General information – Carrier ZONE-MIZER 50ME User Manual
Page 31
Attention! The text in this document has been recognized automatically. To view the original document, you can use the "Original mode".

UNIT
50ME016
50ME024
50ME028
50ME030
VOLTS
KW
MIN IMUM CKT A
Hooting
MP
(Nom) (Unit
Totol)
Cooling
Circ
1
uit
2
Common
200
53
109 8
190.5
_
206 7
230
53
98 9
165.6
—
181 7
460
53
49 5
82.9
-
90.9
200
70
109.8
254.0
—
270.2
230
70
98 9
220.9
-
234 1
460
70
49 5
no 5
-
117.1
200
106
1C9 8
190.5
190.5
397.2
230
106
98 9
165 8
1Ó5.8
344 8
460
106
49.5
165 8
__
172.4
575
106
39.6
132.5
-
138 1
200
53
138 0
190.5
_
233.3
230
53
124 2
165.6
-
207.0
460
53
61 9
82 9
-
103 4
200
70
138 0
254 0
278 0
230
70
124 2
220.9
—
242.9
460
70
61 9
110 5
-
121 5
200
106
138 0
190.5
190 5
405.0
230
106
124 2
165 8
165.8
353 6
460
106
61 9
165.8
176.8
575
106
49 2
132.5
141.5
200
66
168 9
238.1
.
288.0
230
66
151.7
207.1
-
255.2
460
66
75.8
102 8
-
127 2
200
88
168 9
317.3
346.8
230
88
151 7
276.1
302 1
460
88
75 8
138.0
151.0
200
132
168 9
238.3
238 3
506 1
230
132
151 7
207.1
207 1
440.2
460
132
75 8
207.1
—
220 1
575
132
60 2
165.6
-
176 1
200
66
188 0
238 1
—
307.1
230
66
168 9
207.1
—
272 5
460
66
84 5
102.8
-
135 9
200
88
188 0
317.1
346 6
230
88
168 9
276.1
—
307 0
460
88
84 5
138.0
-
153.5
200
132
188 0
238.3
238 3
506.1
230
132
168 9
207 1
207.1
445.0
460
132
84 5
207.1
-
222 6
575
132
67 3
165.6
-
177 7
POWER WIRING DATA
UNIT
SOME 034
50ME040
15 Hp
IFM
20 Hp
IFM
15 Hp
IFM
20 Hp
IFM
15 Hp
IFM
20 Hp
I
IFM !
15Hpj
IFM !
20 Hp
IFM
15 Hp
IFM
20 Hp
IFM
15 Hp
IFM
20 Hps
IFM i
VOLTS
(Nom)
200
230
460
200
230
460
200
230
460
200
230
460
200
230
460
575
200
230
460
575
200
230
460
200
230
460
200
230
460
200
230
460
200
230
460
575
200
230
460
575
KW
(Unit
T otol)
79
79
79
79
79
79
106
106
106
106
106
106
158
158
158
158
158
158
158
158
79
79
79
79
79
79
106
106
106
106
106
106
158
158
158
158
158
158
158
158
MINIMUM CKT AMP
Cool ing
210 8
188 9
94 5
224 6
200 9
100 5
210 8
188 9
94.5
224 6
200 9
100.5
210.9
188.9
94.5
75.6
224 6
200 9
100 5
80 6
247 7
233 5
116 7
261 5
245 5
122 7
247 7
233.5
116 7
261 5
245 5
122 7
247 7
233 7
116 7
95 0
261 5
245.5
122.7
100 0
190.5
165 1
190.5
165.1
285 9
248.5
285.9
248.5
Heating
C ircu it
1
285 9
248 5
124.3
285.9
248 5
124.3
190 5
165.1
165.6
190.5
165 1
165.6
285 9
248 5
248.5
198.8
285 9
248.5
248 5
198.8
285.9
248.5
124.3
285.9
248.5
124.3
190 5
165 1
165 6
190.5
165 1
165.6
285 9
248.5
248 5
198.8
285 9
248.5
248 5
198.8
190 5
165 1
190.5
165.1
285.9
248 5
285.9
248.5
Common
353.8
313.2
156.7
367.6
325 2
162.7
427.0
369.8
185.4
442 0
383.2
192.2
617 8
536.6
268 3
214 8
632 8
550 0
275 1
220.1
390 7
357 8
178 9
404.5
369 8
184 9
438.2
398.6
199 5
452 0
410.3
205.5
628.9
565 0
282.4
227 5
642.7
576 8
288 4
232.5
IFM
— Indoor Air Fan Motor
General information
UNIT
Where a single feeder is to be used, the cooling power tap
may be sized according to the Cooling Minimum Wire Amps
shown in the Power Wiring Data table provided the tap is
10 ft or less in length and enclosed in a raceway.
Similarly, the heating power tap may be sized according
to the Heating Minimum Wire Amps shown in the table pro
vided the tap is 25 ft or less in length and enclosed in a
raceway.
If reheat is necessary for humidity control in all or part
of the modules, use caution in sizing common feeder as
heating and cooling can occur simultaneously in each reheat
module.
For 200/230-volt units, line protection is internal to the
unit. For 460/575-volt units, overcurrent protection must
be provided in each power tap per NEC.