Electrical data
ELECTRICAL DATA, 48MA
UNIT
MODEL
48MA016
48MA024
48MA028
48MA030
48MA034
48MA040
- ' - - -
—
. ....---
-- -
COMPRESSOR
COMPRESSOR
OUTDOOR
COMBUST
INDOOR
POWER
SUPPLY
V/PH/HZ
VOLTAGE
NO 1
Nn 9
FAN MOTOR
FAN
FAN
'--------
--- --
RANHF
—
-
FLA
MOTOR
MOTOR
Min
Max
—
RLA
LRA
CB
RLA
LRA
CB
—
■ ------ - —
Ckt
Fuse
Min
Max
MTA
MTA
No. 1
No. 2
No. 3
FLA
Hp
FLA
Amps
Amps
200/3/60
180
229
63 6
266
89 0*
—
—
—
6 2
6 6
—
5.0
16 2
109 6
125
230/3/60
207
264
57 2
266
80 0*
—
—
—
6.2
60
—
50
13 2
99.5
110
460/3/60
414
528
28 6
120
40 0
—
—
—
6 2
30
—
5 0
6.6
49 8
60
575/3/60
518
660
22 8
96
32 0
—
—
—
6 2
2.4
—
5.0
5 6
39.8
45
200/3/60
180
229
44.4
170
63 0
44 4
170
62 0
62
6 6
_
7 5
24 0
137 5
150
230/3/60
207
264
40 0
170
56 0
40 0
170
56 0
62
60
—
7.5
22 0
124 8
150
460/3/60
414
528
19 9
77
27 8
199
77
27 8
6.2
30
_
7 5
11 0
62 2
70
575/3/60
518
660
15 7
62
22.0
15 7
62
22.0
6.2
2.4
—
7.5
9.0
49.4
60
200/3/60
180
229
63.6
266
89 0
44 4
170
62 0
6 2
6 6
_
100
29 0
168 1
200
230/3/60
207
264
57 2
266
80 0
40 0
170
56 0
6 2
60
—
100
25 0
152 3
175
460/3/60
414
528
28 6
120
40 0
199
77
27 8
6 2
3.0
_
100
12 5
76 1
90
575/3/60
518
660
22.8
96
32 0
15.7
6^
22.0
6.2
2A
—
10.0
9.5
60.4
70
200/3/60
180
229
63 6
266
89 0
63 6
266
89 0
62
6 6
_
100
29 0
187.3
200
230/3/60
207
264
57 2
266
80 0
57 2
266
80 0
6.2
60
—
100
25 0
169 5
200
460/3/60
414
528
28 6
120
41 0
28 6
120
41 0
6.2
30
—
100
12 5
84 2
100
575/3/60
518
660
22 8
96
33 0
22 8
96
33.0
6.2
2.4
—
10.0
9.5
67.5
90
200/3/60
180
229
63.6
266
89 0
63 6
266
89 0
6 2
6.6
6 6
1 8
15.0
46 2
2108
225
20.0
61.0
224 6
250
230/3/60
207
264
57 2
266
80 0
57 2
266
80 0
6 2
60
60
150
46 2
188 9
200
-
20 0
59.4
200.9
250
460/3/60
414
528
28 6
120
40 0
28 6
120
40 0
6 2
3 0
3 0
15 0
21 0
94.5
100
20.0
26 6
100.5
125
575/3/60
518
660
22 8
96
32 0
22 8
96
32 0
6 2
2 4
2 4
150
15.4
75.6
90
20 0
20 0
80 6
100
200/3/60
180
229
80 0
332
1120
80 0
332
1120
62
6 6
6.6
15.0
46 2
247 7
300
-
20.0
61 0
^1 5
300
230/3/60
207
264
77 0
300
106 0
77 0
300
106 0
6 2
60
60
150
46 2
233 5
300
20.0
59.4
245.5
300
460/3/60
414
528
37 3
150
54 0
38 5
150
54 0
62
3 0
3 0
15.0
21.0
1167
150
20.0
26.6
122 7
150
575/3/60
518
660
31 4
120
44 0
31 4
120
44 5
6 2
2 4
2 4
150
154
95 0
125
20 0
20 0
1000
125
CBMTA —
Circuit Breaker Must Trip Amps
FLA
— Full Load Amps
LRA
— Locked Rotor Amps
RLA
— Rated Load Amps
*Unlt has 2 mechanically interlocked circuit breakers Values are for each.
NOTES:
1 Combustion air fan — 115 volts
2 Outdoor fan motor is a 200/230-1-60 motor on all units
t
28