Electrical data, Cont) – Carrier ZONE-MIZER 50ME User Manual
Page 30
Attention! The text in this document has been recognized automatically. To view the original document, you can use the "Original mode".

Electrical data
(cont)
UNIT
SOME
016
and
024
028
and
030
034
and
040
ELECTRIC RESISTANCE HEATER DATA
'
ELEC
HEAT
KW
-
—
---
VOLTS
(3-Ph
60-Hi)
HEATING
FULL LOAD
CB MTA
MAX FUSE
MIN WIRE
ELEMENTS
AMPS PER
EACH
AMPS
AMPS
(Unit
PER ZONE
HEATING
ZONE
EACH
EACH
Total)
MODULE
ELEMENT
MODULE
CIRCUIT
CIRCUIT
200
53
16 5
52
200
190 5
230
53
2
14 4
52
175
165 6
460
53
7 2
45
90
82 9
200
70
22.0
52
300
254 0
230
70
2
19 2
52
225
220 9
460
70
9 6
45
125
1 10.5
200
106
22 0
52
200
190 5
230
106
3
19 2
52
175
165.8
460
106
9 6
45
175
165 8
575
106
7 7
45
150
132 5
200
66
16 5
52
250
238 1
230
66
2
14 4
52
225
207.1
460
66
7 2
45
110
102.8
200
88
22 0
52
350
317.3
230
88
2
19 2
52
300
276 1
460
88
9 6
45
150
138 0
200
132
22 0
52
250
238.3
230
132
19 2
52
225
207.1
460
132
9 6
45
225
207 1
575
132
7 7
45
175
165 6
200
79
16 5
52
300
285 9
230
79
2
14 4
52
250
248 5
460
79
7 2
45
125
124 3
200
106
22 0
52
200
190.5
230
106
2
19 2
52
175
165 1
460
106
9 6
45
175
165 6
200
158
22 0
52
300
285 9
230
158
19 2
52
250
248 5
460
158
o
9 6
45
250
248 5
575
158
7 7
45
200
198 8
CB MTA
— Circuit Breaker Must Trip Amps
NOTE:
Terminal
boards
provided
for
heater
power
wire
connections
are suitable for use with copper or aluminum wire.
t
30