Table 6—heating check chart cont’d – Carrier 38QRA User Manual
Page 8
Attention! The text in this document has been recognized automatically. To view the original document, you can use the "Original mode".

Table 6—Heating Check Chart Cont’d
HEATING OPERATION PRESSURE TABLE, FIXED RESTRICTOR
Unit
38QRA
Indoor Dry
Bulb
Temp (F)
Outdoor Temperature (F) Dry Bulb
60
50
40
30
20
10
0
048
60
High
273.5
239.3
205.2
170.0
170.0
170.1
170.1
Low
82.9
71.3
59.7
47.7
42.2
36.6
30.9
Suction
68.3
57.6
47.0
36.0
31.8
2.6
23.2
70
High
295.2
256.7
218.2
178.5
178.7
179.0
179.2
Low
85.2
71.1
57.1
42.6
38.7
34.9
30.9
Suction
69.5
56.9
44.3
31.3
28.5
25.8
22.9
80
High
314.5
274.0
233.5
191.8
194.3
196.9
199.5
Low
87.2
70.9
54.6
37.8
35.6
33.4
31.1
Suction
70.6
56.1
41.7
26.8
25.5
24.2
22.9
060
60
High
228.9
210.7
192.5
173.8
161.5
149.2
136.6
Low
85.9
74.1
62.2
50.0
41.3
32.5
23.5
Suction
63.3
54.6
45.8
36.8
30.2
23.6
16.8
70
High
258.3
238.7
219.2
199.0
184.9
170.9
156.4
Low
86.9
74.9
62.9
50.5
41.8
33.0
24.0
Suction
65.1
56.1
47.0
37.7
31.0
24.4
17.5
80
High
290.0
268.7
247.4
225.5
209.6
193.6
177.2
Low
88.4
76.0
63.7
50.9
42.2
33.5
24.5
Suction
66.5
57.3
48.2
38.7
31.9
25.2
18.2
Copyright 1991 Carrier Corporation Indpis, IN 46206
13015
Manufacturer reserves the right to discontinue, or change at any time, specifications or designs without notice and without incurring obiigations.
BookI 1 I 4 PC 101
Catalog No. 533-858
Printed in U.S.A.
Form 38QRA-1SI
Pg 8
10-91
Repiaces: New
Tab I5a|5a