Table 7 — minimum fan speeds, Start-up, Table 6 — thermostat anticipator settings (cont) – Carrier 40FS User Manual
Page 16
Attention! The text in this document has been recognized automatically. To view the original document, you can use the "Original mode".

Table 6 — Thermostat Anticipator Settings (cont)
HEATER
MODEL
KW
ANTICIPATOR SETTING
1
St
Stage
2nd Stage
1
St
Stage
2nd Stage
240 V
208 V
240 V
208 V
240 V
208 V
240 V
208 V
40FS916320
CD
5.0
3.75
—
—
.25
.25
—
—
CP
6.0
4.5
—
—
.25
.25
—
—
DA
7.0
5.25
—
—
.25
.25
—
—
DF
7.5
5.63
—
—
.25
.25
—
—
DL
8.0
6.0
—
—
.25
.25
—
—
DX
9.0
6.75
—
—
.25
.25
—
—
EH
10.0
7.5
—
—
.25
.25
—
—
ET*
6.0
4.5
5.0
3.75
.25*
.25*
.25*
.25*
FE*
7.0
5.25
5.0
3.75
.25*
.25*
.25*
.25*
FQ*
8.0
6.0
5.0
3.75
.25*
.25*
.25*
.25*
GB*
9.0
6.75
5.0
3.75
.25*
.25*
.25*
.25*
GM*
10.0
7.5
5.0
3.75
.25*
.25*
.25*
.25*
GY*
8.0
6.0
8.0
6.0
.25*
.25*
.25*
.25*
HJ*
8.5
6.38
8.5
6.38
.25*
.25*
.25*
.25*
HV*
9.0
6.75
9.0
3.75
.25*
.25*
.25*
.25*
JF*
9.5
7.13
9.5
7.13
.25*
.25*
.25*
.25*
JR*
10.0
7.5
10.0
7.5
.25*
.25*
.25*
.25*
40FS916500
EH
10.0
7.5
—
—
.23
.23
—
■
—
GM
15.0
11.3
—
—
.23
.23
—
—
HV
18.0
13.5
—
—
.23
.23
—
—
LW
12.5
9.4
12.5
9.4
.23
.23
.23
.23
PA
15.0
11.25
15.0
11.25
.23
.23
.23
.23
*Heaters that may be wired for 1- or 2-stage operation. When wired for 1-stage operation, add first and second stage anticipator settings.
Table 7 — Minimum Fan Speeds^
FAN
SECTION
HEATER
MIN
FAN
SPEED
MIN
CFM
Model
Kw
240 V
208 V
40FS075
40FS120
40FS920300
10.0
7.5
Low
650
40FS160
40FS916300
8
to
15
6.0
to
11.3
Low
1200
20
and
25
15
and
18.8
Medium
1350
40FS916320
5
to
10
3.75
to
7.5
Low
950
11
to
20
8.75
to
15.0
Medium
950
40FS916500
10
to
18
7.5
to
13.5
Medium
1000
25
and
30
18.8
and
22.5
High
1400
40FQ916
or
38HQ90000
8
and
10
6
and
7.5
Low
1130
15
to
25
11.3
to
18.8
Low
1130
‘Minimum fan speed and cfm for safe eiectric heater operation.
START-UP
Adjust room thermostat as follows:
1. When electric heater is used, set thermostat
anticipator settings according to Table 6. These
settings may be changed slightly to provide a
greater degree of comfort for a particular
installation.
2. Set thermostat selector switch at OFF.
3. Set thermostat fan switch at AUTO, or FAN.
FAN
SECTION
40FS200
or
40FS220
HEATER
Model
40FS920300
40FS916320
40FS916500
40FQ920
or 38HQ90001
(W/40FS200)
40FQ920
(W/40FS220)
Kw
240 V 208 V
10
to
20
25
and
30
5
to
10
11
to
20
10
to
18
25
and
30
10
to
30
10
to
30
7.5
to
15
18.8
and
22.5
3.75
to
7.5
8.25
to
15.0
7.5
to
13.5
18.8
and
22.5
7.5
to
22.5
7.5
to
22.5
MIN
FAN
SPEED
Low
Medium
Low
Medium
Medium
High
Medium
Low
MIN
CFM
1600
1800
1200
1200
1000
1400
1550t
1550
tMinimum cfm is 1960 (High Speed) when 40FS200/40FQ920 is
used with 38RQ054.
4. Turn on main disconnect switch(es) to unit.
5. Set thermostat dial to the desired temperature
(above or below room temperature).
6. Set selector switch at HEAT or COOL.
7. If necessary, adjust the system airflow (cfm) by
changing fan motor speed. See Electrical Data
and Wiring for fan speed adjustment. Refer to
Table 7 for minimum allowable fan speed when
electric heaters are used.
16