Table 4 — Heater Electrical Data and Usage (cent)

FAN

SECTION

ELECTRIC RESISTANCE HEATER (208/240 V)

Model

Branch Circuit

Kw

No.

nUfc

Htr

Amps

Min Wire

Size (AWG)

Max Ft

Wire

Min Gnd

Wire Size

Fuse/CB

Amps

240 V

208 V

240 V

208 V

240 V

208 V

240 V

208 V

240 V

208 V

240 V

208 V

CD

5.0

3.75

1 A

20.8

18.0

8

10

60

45

10

10

35

30

CP

6.0

4.5

1 A

25.0

21.6

8

8

50

60

10

10

40

35

DA

7.0

5.25

1 A

29.2

25.2

6

8

70

50

10

10

45

40

DF

7.5

5.63

1 A

31.3

27.0

6

8

65

50

10

10

45

40

DL

8.0

6.0

1 A

33.3

28.9

6

6

65

70

10

10

50

45

DX

9.0

6.75

1 A

37.5

32.5

6

6

55

65

10

10

60

50

EH

10.0

7.5

1 A

41.6

36.1

4

6

80

60

10

10

60

60

1 A

45.8

39.7

4

6

75

55

8

10

70

60

i ETtt

11.0

8 25

A

25.0

21.6

8

8

50

60

10

10

40

35

■,__ _

iiiSiiPM

8

20.8

18.0

10

10

45

55

10

10

30

25

1 A

50.0

43.4

4

4

70

80

8

10

70

60

1 FEtt

12.0

9.0

2

A

29.2

25.2

6

8

70

50

10

10

45

40

B

20.8

18.0

10

10

45

55

10

10

30

25

1 A

54.2

47.0

2

4

100

70

8

8

80

70

FQtt

13.0

9.75

2

A

33.3

28.9

6

6

60

70

10

10

50

45

B

20.8

18.0

10

10

45

55

10

10

30

25

1 A

58.3

50.5

2

4

100

70

8

8

80

70

GBtt

140

10.5

A

37.5

32.5

6

6

55

65

10

10

60

50

B

20.8

18.0

10

10

45

55

10

10

30

25

1 A

62.5

54.2

2

2

90

100

8

8

90

80

; GMtt

15.0

11.25

2

A

41.6

36.1

4

6

80

60

10

10

60

60

B

20.8

18.0

10

10

45

55

10

10

30

25

1 A

66.7

57.7

2

2

80

90

8

8

90

80

GY .

16.0

12 0

2

A

33.3

28.9

6

6

60

70

10

10

50

45

B

33.3

28.9

6

8

70

55

10

10

45

40

1 A

70.8

61.3

2

2

80

90

8

8

100

90

; HJtt

17.0

12.75

0 A

35.4

30.6

6

6

60

65

10

10

50

45

B

35.4

30.6

6

8

65

50

10

10

45

40

1 A

75.0

64.9

1

2

90

85

8

8

100

90

HVtt

18.0

13.5

A

37.5

32.5

6

6

55

65

10

10

60

50

B

37.5

32.5

6

6

60

70

10

10

50

45

1 A

79.2

68.5

2t

2

70

80

6

8

110

100

JFtt

19.0

14.25

A

39.6

34.3

6

6

55

60

10

10

60

50

B

39.6

34.3

6

6

60

70

10

10

50

45

1 A

83.3

72.2

2t

1

65

95

6

8

110

100 •

JRt+

20.0

15 0

2 A

41.6

36.1

4

6

80

60

10

10

60

60

B

41.6

36.1

6

6

55

65

10

10

60

50

EH

10.0

7.5

1

24.0

20.8

8t

8t

70

60

10

10

40

35

GM

15.0

11.3

1

36.0

31.3

6t

8t

65

40

10

10

60

45

HV

18.0

13.5

1

43.3

37.5

6t

6t

55

55

10

10

60

60

LW ■

18.8

1

60.2

52.2

4

4

65

65

8

8

90

80

PA

: 30.0 ;

22 5

1

72.2

62.5

2

4

90

55

8

8

100

90

40FS160,

40FS200

or

40FS220

40FS916320

40FS916500

(3-Ph)

Two-stage electric heaters. Remaining heaters are single-
stage. See Fig. 15.

CB

— Circuit Breaker

^Circuit breaker models. All remaining models over 10 kw are in­

ternally fused.

tCopper wire sizes based on 75 C; all other copper wire sizes

based on 60C. Use copper wire only.

JCopper wire rated at 75 C and no larger than 00 size must

be used.

**Use fuses only on 40FS91 6300 DL, DX, EH, 40FQ91 6010,020,

40FQ920060 and 40FS920300 EH units.

tfStandard heater models that require 2 line power circuits. Add

accessory conversion lug set for single power circuit operation.

NOTES:

1. Heater models 40FQ916, 40FQ920 and 40FS916320 equipped

with 60-va control circuit transformer. Remaining heater
models have 40-va transformer.

2. Field-selected wire sizes must not create a voltage drop

between power source and unit in excess of 2% of unit
rated voltage.