3.6 APPLICABLE STANDARDS


BS EN 60068-2-1
(Minimum temperature)

-30

°

C (-22

°

F)

BS EN 60068-2-2
(Maximum temperature)

+70

°

C (158

°

F)

BS EN 60950

Safety of information technology equipment, including electrical business
equipment

BS EN 61000-6-2

EMC Generic Immunity Standard (Industrial)

BS EN 61000-6-4

EMC Generic Emission Standard (Industrial)

BS EN 60529
(Degrees of protection
provided by enclosures)

IP65 when mounted into panel with optional gasket
IP42 when mounted into panel WITHOUT gasket

UL508
NEMA rating

Enclosure type 2 when mounted into panel WITHOUT gasket
Enclosure type 12 when mounted into panel with gasket

In line with our policy of continual development, Deep Sea Electronics, reserve the right to change specification without notice.

4 INSTALLATION

4.1 USER CONNECTIONS

4.1.1 CONNECTOR A

Terminal Function

Recommended size

1

DC supply positive

1.0mm² (AWG 18)

2

DC supply negative

1.0mm² (AWG 18)

3

Screen

DSEnet only

4

A

0.5mm² (AWG 20)

DSEnet only

5

B

0.5mm² (AWG 20)

DSEnet only

4.2 SCHEMATIC INTERCONNECTION DIAGRAM