4 installation, 6 applicable standards, 1 user connections – Winco DSE2548 User Manual
Page 7: 2 schematic interconnection diagram
DSE2548 relay output expansion module
057-083 Issue 1 DSE2548 LED expansion operator manual 7
3.6 APPLICABLE STANDARDS
BS EN 60068-2-1
(Minimum temperature)
-30
°
C (-22
°
F)
BS EN 60068-2-2
(Maximum temperature)
+70
°
C (158
°
F)
BS EN 60950
Safety of information technology equipment, including electrical business
equipment
BS EN 61000-6-2
EMC Generic Immunity Standard (Industrial)
BS EN 61000-6-4
EMC Generic Emission Standard (Industrial)
BS EN 60529
(Degrees of protection
provided by enclosures)
IP65 when mounted into panel with optional gasket
IP42 when mounted into panel WITHOUT gasket
UL508
NEMA rating
Enclosure type 2 when mounted into panel WITHOUT gasket
Enclosure type 12 when mounted into panel with gasket
In line with our policy of continual development, Deep Sea Electronics, reserve the right to change specification without notice.
4 INSTALLATION
4.1 USER CONNECTIONS
4.1.1 CONNECTOR A
Terminal Function
Recommended size
1
DC supply positive
1.0mm² (AWG 18)
2
DC supply negative
1.0mm² (AWG 18)
3
Screen
DSEnet only
4
A
0.5mm² (AWG 20)
DSEnet only
5
B
0.5mm² (AWG 20)
DSEnet only
4.2 SCHEMATIC INTERCONNECTION DIAGRAM