beautypg.com

4 dsenet, 5 dimensions – Winco DSE2548 User Manual

Page 6

background image

DSE2548 relay output expansion module

6 057-084 Issue 1 DSE2548 LED expansion operator manual


3.4 DSENET®


DSEnet is the interconnection cable between the host controller and the expansion module(s) and
must not be connect to any device other than DSE equipment designed for connection to the DSEnet.

Cable type

Two core screened twisted pair

Cable characteristic impedance

120

Recommended cable

Belden 9841
Belden 9271

Maximum cable length

1000m (1km) when using Belden 9841 or direct equivalent.
500m (0.5km) when using Belden 9271 or direct equivalent.

DSEnet topology

Bus with no stubs (spurs)

DSEnet termination

120

. Fitted internally to host controller. Must be fitted externally

to the ‘last’ expansion module by the customer .

Maximum expansion modules

Refer to host controller documentation

NOTE : As a termination resistor is internally fitted to the host controller, the host controller
must be the ‘first’ unit on the DSEnet. A termination resistor MUST be fitted to the ‘last’ unit on
the DSEnet. See the section entitled‘Typical Wiring Diagram’
elsewhere in this manual for
details.


3.5 DIMENSIONS


Overall size

180.0mm x 116.0mm x 42.7mm
(7.07” x 4.57” x 1.68”)

Mounting type

Panel mounting

Panel cutout

154mm x 98mm
(6.06” x 3.86”)