beautypg.com

Viconics R842 User Manual

Page 5

background image

5

1

High voltage blue wire is always connected. R842 units are powered devices.

2

Provide overload protection and disconnect as required.

3

Do not use 24 Vac terminal #1 as power supply to an electronic thermostat. Use a separate transformer.

4

L1, L2 & L3 can be mixed / matched.

5

Operates only if all relays control the same phase of a 3 phase system or on a single phase branch.

Multiple two wire low voltage thermostats using the

same separate 24 Vac transformer to control

multiple R842 baseboard relays

Viconics T186 sensor to control

one R842 baseboard relay




















Viconics T186 sensor for

master / slave arrangement of R842 baseboard relays

Model

Volt

Resistive

Rating (A)

Inductive

Rating (HP)

R842-120 120

22

½ HP

8 Amp

R842-208 208

22

1 HP

8.8 Amp

R842-240 240

22

1 HP

8 Amp

R842-277

277 19 N/A

R842-347

347 18 N/A


Electrical Specifications:



















R842-600

600 10 N/A

Baseboard(s) / load(s)

One

Relay(s)

One

T186 thermostat

One

Baseboard(s) / load(s)

Multiple

Relay(s)

Multiple

Thermostat(s)

Multiple

Transformer

External

Adjust thermostat
anticipator to 0.1 A
or less.

Load side

RED

BLACK

BLUE

Internal circuit

RED

BLACK

BLUE

Internal circuit

RED

BLACK

BLUE

Internal circuit

L1

L2 / N

Load side

Load side

2 wire low

voltage thermostats

L1

L2 / N

Separate remote

24 Vac

transformer

Set both switch
on all relays
to factory default
ON position

1

2

ON

1

2

ON

1

2

ON

3

2

1

3

2

1

3

2

1

Junction box

Load side

RED

BLUE

Internal circuit

L1

L2 / N

T186 sensor

2 wire non polarized

Set both switch on relay
to OFF position

1

2

ON

3

2

1

BLACK

Baseboard(s) / load(s)

Multiple

Relay(s)

Multiple

T186 Thermostat

One

Note: Slave units life cycle is
100,000 cycles

RED

BLACK

BLUE

Internal circuit

1

2

3

1

RED

BLACK

BLUE

Internal circuit

1

2

3

RED

BLACK

BLUE

Internal circuit

1

2

3

1

1

L1

L2 / N

2

Load side

3

3

3

5

Install a jumper
across terminals
1 and 3 on all
slave relays

1

2

ON

Set both switch
on master relay
to OFF position

1

2

ON

1

2

ON

Master

Slave(s)

Load side

Load side

Maximum of 10 slave units

Set both switch
on slave relays
to factory default
ON position

T186 sensor

2 wire non polarized