Installer configuration parameter menu
Configuration is done locally at the repeater.
• To enter configuration, press and hold the Left button for 8 seconds
• Press again the Left button repetitively to scroll between all the available parameters
• Use the (up / right) and (down / middle / center) key to change the parameter to the desired value.
• To acknowledge and save the new value, press the Left button again.
• The next listed parameter is now displayed
Configuration interface
Left
Enters the configuration mode. Press and hold for 8 seconds
Pressing repetitively will scroll all available parameters one by one
Middle / Center
Adjust / rotate parameter value down
Right
Adjust / rotate parameter value up
Configuration parameters
Default value
Significance and adjustments
Com Addr
Repeater networking address
Default value =
254
Range is: 0 to 254 Valid range is 0 to 254
PAN ID
Personal Area Network Identification
Default value = 0
Range is:
0 to 500
This parameter (Personal Area Network Identification) is used to link specific
controllers or repeaters to a single specific Viconics wireless gateway ( VWG /
JACE ) For every controller or repeater reporting to a gateway be sure you set
the
SAME PAN ID value both at the gateway and the wireless device(s).
The default value of 0 is
NOT a valid PAN ID. The valid range of available PAN
ID is from 1 to 500
Channel
Channel selection
Default value = 10
Range is:
10 to 26
This parameter (Channel) is used to link specific controllers or repeaters to
specific Viconics wireless gateway(s) ( VWG / JACE ) For every controller or
repeater reporting to a gateway be sure you set the
SAME channel value both at
the gateway and the wireless device(s).
Viconics recommends using only the following channels ( 15, 25 or 26 )
The default value of 10 is
NOT a valid channel. The valid range of available
channel is from 11 to 26