VST5000W5000W
Wireless Survey Tools User Guide
• In order to avoid interference from other wireless
devices such as (wireless routers, wireless adapters
or laptop using wireless networks, etc.) insure that a
minimum distance of 3 feet or 1 meter is maintained
between any Viconics node and any Wi-Fi devices.
Maintain a distance of 10 feet or 3 meters or more
would be preferable when possible (fig. 3).
VWG in a metal box. If the VWG needs to be installed
inside a metal cabinet, use the remote antenna
accessory.
The recommended maximum number of wireless controllers
per JACE is 30; a minimum of 3 controllers should be within
50 feet or 15 Meters of the VWG (fig. 4 -5).
• Ensure that at least one controller
is within 50 feet (15 M) of the VWG
for every cluster of 10 controllers
installed.
• Always install the VWG closest to
the center of all associated wireless
controllers.
• Always locate the VWG near or in the
direct line of sight to as many wireless
controllers as possible.
• Avoid metal, brick walls or concrete
obstructions between wireless devices
as much as possible.
• Make sure the antenna on the VWG is
perpendicular to the floor.
• Avoid placing the VWG and the
controllers near metal or enclosing the
t
t
t
t
t
Beyond Comfort
t
t
t
t
t
G
At least 1 Viconics
controller node
to be within 50
feet (15M) of the
VWG for every
other 10 controller
installed.
Fig. 5
Fig. 4
50 feet (15 M)
maximum
10 feet (3 M)
Preferably 10 feet (3 M) or more between Wi-Fi
equipment and Viconics wireless devices
3 feet (1 M)
Minimum 3 feet (1 M) between Wi-Fi
equipment and Viconics wireless devices
Fig. 3