beautypg.com

Screw terminal arrangement and wiring, Typical applications, Main outputs wiring – Viconics VZ7656H Wireless Installation Guide User Manual

Page 7

background image

7 | VZ7656R & VZ7656H-Installation Guide

Screw terminal arrangement and wiring

T

YPICAL

A

PPLICATIONS


Main outputs wiring

Wiring notes:

Note 1: If the same power source is used for the heating stages, install jumper across RC &

RH. Maximum current is 2.0 amps.

Note 2: If auxiliary output is used to toggle occupancy of the electronic control card inside

the equipment, configure the relay parameter (Aux cont) to the N.O. setting. A
second relay can be added for additional functionality of the occupancy output.

Note 3: Analog outputs and inputs use a half bridge rectifier. Reference of the control

signal is the common of the power supply of the Terminal Equipment Controller.
(Terminal C)

Note 4: Electromechanical contacts are to be used with the digital inputs. Electronic triacs

cannot be used as mean of switching for the input. The switched leg to the input for
the input to activate is terminal C (common)

Note 5: The transformer of the unit provides power to the t Terminal Equipment Controller

and the additional loads that will be wired to the Terminal Equipment Controller.


BPD

Aux

SP

DI1

RS

SCom

OS

DS

G

Y1

Y2

W2

W1

RH

C

RC

VZ7656R Controller Terminals

BPD

Aux

SP

DI1

RS

SCom

OS

DS

G

Y1

Y2

O/B

W1

RH

C

RC

VZ7656H Controller Terminals