25 | VZ7656R & VZ7656H-Installation Guide

Prog rec

Progressive recovery

enabled

Default value = Off

Progressive recovery is
automatically disabled if
BI 1 is configured remote
NSB

Off, = no progressive recovery.

The configured occupied schedule time is the time at which the

system will restart and send the occupied status to the attached

zones.

On, = progressive recovery active.

The configured occupied schedule time is the time at which the
desired occupied temperature setpoints will be attained at the
Zones. The RTU controller will automatically optimize the
equipment start time.

Occ CL

Return air sensor network

lost occupied cooling

setpoint

Default: 75°F

If network communication is lost with the zone controllers, the

return air sensor will control the RTC to maintain this setpoint.

54°F to 100°F (12°C to 37.5°C)

(increments: 0.5° or 5°)

Occ HT

Return air sensor network

lost occupied heating

setpoint

Default: 72°F

If network communication is lost with the zone controllers, the

return air sensor will control the RTC to maintain this setpoint.

40 to 90°F (4.5°C to 32°C)
(increments: 0.5° or 5°)

Unocc CL

Return air sensor

network lost unoccupied

cooling setpoint

Default: 82°F

If network communication is lost with the zone controllers, the

return air sensor will control the RTC to maintain this setpoint.

54 to 100°F (12°C to 37.5°C)

(increments: 0.5° or 5°)

Unocc HT

Return air sensor network

lost unoccupied heating

setpoint

Default: 65°F

If network communication is lost with the zone controllers, the

return air sensor will control the RTC to maintain this setpoint.

40 to 90°F (4.5°C to 32°C)
(increments: 0.5° or 5°)

Sp range

Static Pressure sensor
range

Default: 0

Static pressure transducer range. Voltage input range is 0 to 5
VDC.

0 = 0 to 1.5 in WC
1 = 0 to 2 in WC
2 = 0 to 3 in WC
3 = 0 to 4 in WC

4 = 0 to 5 in WC