Viconics VZ7656H Wireless Installation Guide User Manual
Page 25
25 | VZ7656R & VZ7656H-Installation Guide
Prog rec
Progressive recovery
enabled
Default value = Off
Progressive recovery is
automatically disabled if
BI 1 is configured remote
NSB
Off, = no progressive recovery.
The configured occupied schedule time is the time at which the
system will restart and send the occupied status to the attached
zones.
On, = progressive recovery active.
The configured occupied schedule time is the time at which the
desired occupied temperature setpoints will be attained at the
Zones. The RTU controller will automatically optimize the
equipment start time.
Occ CL
Return air sensor network
lost occupied cooling
setpoint
Default: 75°F
If network communication is lost with the zone controllers, the
return air sensor will control the RTC to maintain this setpoint.
54°F to 100°F (12°C to 37.5°C)
(increments: 0.5° or 5°)
Occ HT
Return air sensor network
lost occupied heating
setpoint
Default: 72°F
If network communication is lost with the zone controllers, the
return air sensor will control the RTC to maintain this setpoint.
40 to 90°F (4.5°C to 32°C)
(increments: 0.5° or 5°)
Unocc CL
Return air sensor
network lost unoccupied
cooling setpoint
Default: 82°F
If network communication is lost with the zone controllers, the
return air sensor will control the RTC to maintain this setpoint.
54 to 100°F (12°C to 37.5°C)
(increments: 0.5° or 5°)
Unocc HT
Return air sensor network
lost unoccupied heating
setpoint
Default: 65°F
If network communication is lost with the zone controllers, the
return air sensor will control the RTC to maintain this setpoint.
40 to 90°F (4.5°C to 32°C)
(increments: 0.5° or 5°)
Sp range
Static Pressure sensor
range
Default: 0
Static pressure transducer range. Voltage input range is 0 to 5
VDC.
0 = 0 to 1.5 in WC
1 = 0 to 2 in WC
2 = 0 to 3 in WC
3 = 0 to 4 in WC
4 = 0 to 5 in WC