Typical applications

Schematic Wiring

Settings

2 pipe system cooling and/or heating: VT7300A5x00(x), VT7300C5x00(x) & VT7305C5x00(x) On / Off N.C. actuator

Mandatory
• Pipe no = 2 pipes
• CntrltTyp = On/Off
• Fan Menu = 0 (L-M-H)
• FL time = as per actuator

If cooling only set::
• SeqOpera = 0 Cooling only

If heating only set::
• SeqOpera = 1 Heating only

If heat / cool auto-changeover with
a local water temperature sensor set:

SeqOpera = 0 Cooling only

UI3 = COS

2 pipe system cooling and/or heating: VT7300C5x00(x) & VT7305C5x00(x) Floating actuator

Mandatory
• Pipe no = 2 pipes
• CntrltTyp = Floating
• Fan Menu = 0 (L-M-H)
• FL time = as per actuator

If cooling only set::
• SeqOpera = 0 Cooling only

If heating only set::
• SeqOpera = 1 Heating only

If heat / cool auto-changeover with
a local water temperature sensor set:
• SeqOpera = 0 Cooling only
• UI3 = COS

2 pipe system cooling and/or heating: VT7300F5x00(x) & VT7305F5x00(x) Analog actuator

Mandatory
• Pipe no = 2 pipes
• Fan Menu = 0 (L-M-H)
• RA/DA = as per actuator

If cooling only set::
• SeqOpera = 0 Cooling only

If heating only set::
• SeqOpera = 1 Heating only

If heat / cool auto-changeover with
a local water temperature sensor set:
• SeqOpera = 0 Cooling only
• UI3 = COS

0 to 10

Vdc

UI3 COS

0 V~ Com

24 V~ Hot

AO1

Optional supply water

temperature sensor

Fan-L

Fan-M

Fan-H

High

Med

Low

24 Vac fan relays

Modulating Analog

Valve Cooling and/or Heating

Room Temperature
Control Thermostat

3 Speed fan

Modulating Floating

Valve Cooling and/or Heating

Room Temperature
Control Thermostat

3 Speed fan

Optional supply water

temperature sensor

UI3 COS

24 V~ Com

24 V~ Hot

BO1 Open

BO2 Close

Fan-L

Fan-M

Fan-H

High

Med

Low

24 Vac fan relays

Normally Closed On/Off

Valve Cooling and/or Heating

Room Temperature
Control Thermostat

3 Speed fan

Optional supply water

temperature sensor

UI3 COS

24 V~ Com

24 V~ Hot

BO2 N.C.

Fan-L

Fan-M

Fan-H

High

Med

Low

24 Vac fan relays