Installer configuration parameter menu
Configuration can be done through the network or locally at the thermostat.
• To enter configuration, press and hold the middle button (°C/°F or Override) for 8 seconds
• Press the same middle button repetitively to scroll between all the available parameters
• Use the up and down key to change the parameter to the desired value.
• To acknowledge and save the new value, press the middle button again.
• The next listed parameter is now displayed

Configuration interface

Fan

Re-starts the configuration parameter list at the beginning

°C/°F
Override

Enters the configuration mode. Press and hold for 8 seconds

Pressing repetitively will scroll all available parameters one by one

Down

Adjust / rotate parameter value down

Up

Adjust / rotate parameter value up



User interface

Unoccupied mode Override
An Override can be made on commercial models during an Unoccupied period. If the Override option is enabled in the
lockout configuration pressing the middle override button will resume occupied setpoints for a time specified by
parameter ToccTime

Keypad interface

System

Is used to toggle between the different system mode available as per sequence and menu selected

Pressing repetitively the button will toggle between all the available modes
Available menus are dependent on selected sequence of operation

Fan

Is used to toggle between the different fan mode available as per sequence and menu selected

Pressing repetitively the button will toggle between all the available modes
Available menus are dependent on selected sequence of operation and menu selected for Fan

°C/°F

Override

Middle key is

• °C / °F for Hotel models
• Override for commercial models

Down

Adjust the setpoints down

In cooling mode only the cooling setpoint displayed,
In heating mode only the heating setpoint displayed
In auto mode, (See below)

Up

Adjust the setpoints up

In cooling mode only the cooling setpoint displayed,
In heating mode only the heating setpoint displayed
In auto mode, (See below)

1. Any setpoint change can be permanent or temporary based on configuration parameter (Setpoint Type)
2. Any setpoint written through the network, will be permanent and cancel any active temporary setpoints

3.

Lockouts of access to certain functions is made with configuration parameter (lockout)

Occupied setpoint adjustments

Cooling
mode

Heating
mode

Off mode

Auto Mode
• Setpoint presented to user is the setpoint from the last

action taken by the thermostat or the one currently in use.

• If the other setpoint is the one desired, then the MODE

button is used to toggle between the current displayed one
and the other.

Cool XX.X °F or
°C

Heat XX.X °F or
°C

No access to
setpoint

Cool XX.X °F or °C or Heat XX.X °F or °C
Toggle to ( Heat or Cool )with MODE button

• Heat/Cool setpoint toggle with MODE button to be active only in AUTO mode.
• If cooling, heating or off mode is active, function is disabled

Unoccupied and Stand-By setpoints adjustments
Setting the stand-by and unoccupied setpoints is done through the network or through configuration setup only.