• Mode button menu sequence.
-
Modes presented to the user are dependent on sequence of operation selected
-
Default mode is in bold when sequence of operation parameter is changed
-
* Auto mode menu can be disabled with (AutoMode) parameter
Sequence selected
Mode Menu
0 = Cooling only
Off - Cool
1 = Heating only
Off - Heat
2 = Cooling With Reheat
Off – Auto *– Heat – Cool
3 = Heating With Reheat
Off - Heat
4 = Cooling / Heating 4 pipes
Off – Auto *– Heat – Cool
5 = Cooling / Heating 4 pipes with Reheat
Off – Auto *– Heat – Cool
* Auto. The Auto mode can be disabled from the menu with the (AutoMode) parameter
• Available fan button menu sequences.
Fan button menu
configuration
Menu presented are dependent on model used
and sequence of operation selected
Default value when
sequence toggled
0 Low-Med-High
3 Speed configuration using 3 fan relays ( L-M-H )
High
1 Low-High
2 Speed configuration using 2 fan relays ( L-H )
High
2 Low-Med-High-Auto
3 Speed configuration with Auto fan speed mode using 3 fan relays ( L-M-H )
High
3 Low-High-Auto
2 Speed configuration with Auto fan speed mode using 2 fan relays ( L-H )
High
4 On-Auto
Single Speed configuration. Auto is for Fan on demand / On is On all the time
Auto
Auto speed fan mode is also offered in heating mode applications; it will not however have any effect on dehumidification. It will be
strictly for noise comfort issues
Configuration parameters
Default value
Significance and adjustments
Com Addr
Thermostat networking address
Default value = 4
Range is: 0 to 254
Conditional parameter to BACnet MS-TP models (VT730xX1000B)
Conditional parameter to Wireless models (VT730xX1000W)
This parameter will only appear when a BACnet or wireless network adapter is
present. If the thermostat is installed as a stand-alone unit or with an Echelon
adapter, this parameter will not be used or displayed
• For BACnet MS-TP models valid range to use is from 1 to 127
• For wireless models valid range is 0 to 254 with a maximum of 40 thermostat per
VGG
PAN ID
Personal Area Network
Identification
Default value = 0
Range is: 0 to 500
Conditional parameter to Wireless models (VT730xX1000W)
This parameter will only appear when a wireless network adapter is present. If the
thermostat is installed as a stand-alone unit or with a BACnet or Echelon adapter,
this parameter will not be used or displayed
This parameter (Personal Area Network Identification) is used to link specific
thermostats to a single specific Viconics wireless gateway ( VWG ) For every
thermostat reporting to a gateway ( maximum of 40 thermostats per gateway ), be
sure you set the SAME PAN ID value both at the gateway and the thermostat(s).
Channel
Channel selection
Default value = 10
Range is: 10 to 26
Conditional parameter to Wireless models (VT73x0X1000W)
This parameter will only appear when a wireless network adapter is present. If the
thermostat is installed as a stand-alone unit or with a BACnet or Echelon adapter,
this parameter will not be used or displayed
This parameter (Channel) is used to link specific thermostats to specific Viconics
wireless gateway(s) ( VWG ) For every thermostat reporting to a gateway (
maximum of 40 thermostats per gateway ), be sure you set the SAME channel
value both at the gateway and the thermostat(s).
Viconics recommends using only the 2 last channels ( 25-2575MHz and 26-
2580MHz )
The default value of 10 is NOT a valid channel. The valid range of available
channel is from 11 to 26