beautypg.com

Viconics VT7300 Installation Manual (First Release 1000 Series) User Manual

Page 11

background image

11

Mode button menu sequence.

-

Modes presented to the user are dependent on sequence of operation selected

-

Default mode is in bold when sequence of operation parameter is changed

-

* Auto mode menu can be disabled with (AutoMode) parameter

Sequence selected

Mode Menu

0 = Cooling only

Off - Cool

1 = Heating only

Off - Heat

2 = Cooling With Reheat

Off – Auto *– Heat – Cool

3 = Heating With Reheat

Off - Heat

4 = Cooling / Heating 4 pipes

Off – Auto *– Heat – Cool

5 = Cooling / Heating 4 pipes with Reheat

Off – Auto *– Heat – Cool

* Auto. The Auto mode can be disabled from the menu with the (AutoMode) parameter


Available fan button menu sequences.

Fan button menu
configuration

Menu presented are dependent on model used

and sequence of operation selected

Default value when
sequence toggled

0 Low-Med-High

3 Speed configuration using 3 fan relays ( L-M-H )

High

1 Low-High

2 Speed configuration using 2 fan relays ( L-H )

High

2 Low-Med-High-Auto

3 Speed configuration with Auto fan speed mode using 3 fan relays ( L-M-H )

High

3 Low-High-Auto

2 Speed configuration with Auto fan speed mode using 2 fan relays ( L-H )

High

4 On-Auto

Single Speed configuration. Auto is for Fan on demand / On is On all the time

Auto

Auto speed fan mode is also offered in heating mode applications; it will not however have any effect on dehumidification. It will be
strictly for noise comfort issues


Configuration parameters
Default value

Significance and adjustments

Com Addr
Thermostat networking address
Default value = 4
Range is:
0 to 254

Conditional parameter to BACnet MS-TP models (VT730xX1000B)
Conditional parameter to Wireless models (VT730xX1000W)
This parameter will only appear when a BACnet or wireless network adapter is
present. If the thermostat is installed as a stand-alone unit or with an Echelon
adapter, this parameter will not be used or displayed
• For BACnet MS-TP models valid range to use is from 1 to 127

• For wireless models valid range is 0 to 254 with a maximum of 40 thermostat per

VGG

PAN ID
Personal Area Network
Identification
Default value = 0
Range is:
0 to 500

Conditional parameter to Wireless models (VT730xX1000W)
This parameter will only appear when a wireless network adapter is present. If the
thermostat is installed as a stand-alone unit or with a BACnet or Echelon adapter,
this parameter will not be used or displayed

This parameter (Personal Area Network Identification) is used to link specific
thermostats to a single specific Viconics wireless gateway ( VWG ) For every
thermostat reporting to a gateway ( maximum of 40 thermostats per gateway ), be
sure you set the SAME PAN ID value both at the gateway and the thermostat(s).

Channel
Channel selection
Default value = 10
Range is:
10 to 26

Conditional parameter to Wireless models (VT73x0X1000W)
This parameter will only appear when a wireless network adapter is present. If the
thermostat is installed as a stand-alone unit or with a BACnet or Echelon adapter,
this parameter will not be used or displayed

This parameter (Channel) is used to link specific thermostats to specific Viconics
wireless gateway(s) ( VWG ) For every thermostat reporting to a gateway (
maximum of 40 thermostats per gateway ), be sure you set the SAME channel
value both at the gateway and the thermostat(s).

Viconics recommends using only the 2 last channels ( 25-2575MHz and 26-
2580MHz )

The default value of 10 is NOT a valid channel. The valid range of available
channel is from 11 to 26