APPENdIx A: TERmINAL CORRESPONdANCE
The terminals of an VT8600 are identified diifferently and have a wider range of possible functions compared to those of any of the
VT7000 series Room Controllers. Nonetheless, there is a direct correspondance of functions between the terminals of the VT7000
series and the VT8600 series. Consult the table below to verify the appropriate terminal when replacing a VT7000 Room Controller
with a VT8600 Room Controller.
VT7000
VT8600
Terminal name
Terminal ID
Terminal name
Terminal ID
Binary Input 1
BI1
Universal Input 16
UI16
Binary Input 2
BI2
Universal Input 17
UI17
Universal Input 3
UI3
Universal Input 19
UI19
Sensor Common
Scom
Terminal 18 Common
COM
Remote Sensor
RS
Universal Input 20
UI20 - RS
Sensor Common
Scom
Terminal 21 Common
COM
Mix/Supply Sensor
MS
Universal Input 22
UI22 - SS
APPENdIx B: POWER OUTAGE CLOCk RESET
In the event of a power outage, VT8600 Room Controllers will retain the correct time as long as the duration of the power outage is
not prolonged. Depending on the duration of the power outage, the Room Controller's internal clock may need to be updated or reset
completely. The following table gives an indication of the expected clock performance after a power outage of a given duration.
Outage duration
Room Controller behaviour
0 - 24 hours
Clock functions are normal
24 - 36 hours
Clock accuracy not guaranteed, time may need to be adjusted
36 - 72 hours
Clock no longer increments and will need to be adjusted when power is
restored.
72+ hours
Clock functions are fully reset, and will need to be reinitialized as per a
new installation.