[e] Adjustment at Part Replacement
The thermistor and electronic controller are designed for optimum ice production. If adjustment
is desired at part replacement, follow the instructions below.
The variable resistor VR1 is for a fine adjustment of the defrost cycle completion temperature.
It needs no adjustment at part replacement.
The variable resistor VR2 is for a fine adjustment of the freeze cycle completion temperature.
Turn VR2 clockwise for a higher temperature (WARM), i.e. ice cubes with larger diameter
holes and counterclockwise for a lower temperature (COLD), i.e. ice cubes with smaller
diameter holes.
Note: Do not adjust VR2 to the lowest temperature. It will cause excessive ice production
resulting in defrost failure.
Fig. 8
Electronic Controller
Variable resistor for
adjustment of freeze cycle
completion temperature
Variable resistor for
adjustment of defrost cycle
completion temperature
(Does not need adjustment)