Start-Up Procedures
Error (Hard Lockout) Mode
If a system fault occurs while the boiler is run-
ning, the system goes into lockout and the dis-
play starts to flash with the first digit as an E
and the next two digits give the code for this
fault.
For a detailed description of the error codes, ref-
erence the PRESTIGE Troubleshooting Guide.
The boiler freeze protection feature is
disabled during a Hard Lockout, howev-
er the CH circulator will operate and the
3-way valve will open to the CH system.
During a hard lockout or low water con-
dition the boiler will not re-start without
service. If the heating system is left unat-
tended in cold weather appropriate safe-
guards or alarms should be installed to
prevent property damage.
CAUTION
CAUTION
Gas valve harness not properly connected
Failed ignition after 5 attempts
Power supply lost after lockout occured
Internal control failure
Internal control failure
E
E
0
2
03
0
4
0
8
0
9
E
E
E
Display
Hard Lockout
Internal control failure
0
5
E
Internal control failure
0
6
E
Internal control failure
0
7
E
Flame detected prior to burner startup
E
0
0
Internal control failure
External limit (terminals 13 & 14) is OPEN
Blower signal does not reset to zero
No blower signal present
Supply Temperature sensor is short circuited
1
1
1
2
1
5
1
6
29
28
E
E
E
E
E
E
Flue Temperature exceeds 250 F
52
E
Internal control error - failure to read parameters
61
E
Return Temperature sensor is short circuited
Supply Temperature sensor is OPEN
Return Temperature sensor is OPEN
Internal control failure
Internal control failure
Inadequate power supply to the fan
E
E
31
32
36
37
44
60
65
E
E
E
E
E
Flue Temperature sensor is short circuit
40
E
Return Temperature exceeds 212 F
Supply Temperature increased too rapidly
Internal control failure
Contact Triangle Tube Service Department
Internal control failure
Internal control failure
Internal control failure
1
7
1
9
25
1
3
E
E
E
E
Supply Temperature exceeds 212 F
1
8
E
Return Temperature is higher than supply temperature
24
E
E
1
4
Flue Temperature sensor is OPEN
35
E
E
Internal control failure
15
E
Supply or Return Temperature sensor drift
23
Invalid power frequency
Supply or Return Temperature failure
Supply or Return Temperature not changing
13
1
1
1
1
1
22
24
E
E
E