External wiring, Fig. 21: secondary system circulator wiring – TriangleTube Prestige Excellence Part 1 User Manual
Page 38
![background image](/manuals/714825/38/background.png)
System Circulator - Zone Valve Application
To energize the system circulator shown as
item 12 in Fig. 10 page 19 reference Fig. 21.
Installer to provide a Transformer / Relay such
as Honeywell R8285 or equivalent and Zone
Valves with isolated end switch such as
Honewell V8043 or equivalent.
External Modulating Control
The Prestige EXCELLENCE firing rate can be
controlled by an external modulating boiler
controller. See page 29 for wiring and page 51
for control module setup.
Outdoor Reset Control
1. The PRESTIGE Excellence may operate
with a variable boiler operating tempera-
ture using the Triangle Tube outdoor sen-
sor, see pages 47 through 50 for installation
and setup.
If the installer opts for a fixed operating
temperature for the boiler system, the
outdoor sensor is not required and
should not be installed.
Additional 24V Limit Wiring
The PRESTIGE Excellence provides 24V ter-
minal connections for additional limit controls
as shown in Fig. 20 page 29. These limit ter-
minal connections will provide a "hard" lock-
out requiring a manual reset of the PRESTIGE
Excellence control, or a “soft” lockout in
which the PRESTIGE Excellence will auto-
matically reset.
NOTICE
24 V
Transformer
by Others
Honeywell V8043
Zone Valves
or Equivalent
Honeywell R8285D
Transformer / Relay
or Equivalent
24V Terminal Strip
System Circulator
24V Low Voltage Wiring
120V High Voltage Wiring
Room Thermostats
H
N
120V
R
C
G
1
3 4
6
7
8
To Prestige
Fig. 21: Secondary System Circulator Wiring
External Wiring
31