TO TEMPORARILY PLACE THE BURN-
ER INTO LOW FIRE TEST MODE: press
the MODE button until “
StbY
” is displayed.
Then press and hold both the MODE and “-”
button simultaneously until the first digit flash-
es “L”.
TO DEACTIVATE THE HIGH OR LOW
FIRE TEST MODE: Press and hold the “+”
and “-” button simultaneously to deactivate the
high or low fire test mode. While in the
“
StbY
” mode:
If the “+” button is held in the CH sys-
tem (parameter 3) will be turned OFF
and the display will show “
cOFF
”.
Press and hold the “+” button to turn the
CH system back ON, the display will
show “c” followed by CH set point tem-
perature (parameter 4) or CH target
temperature. If the “-” button is held in
while in the “
StbY
” mode domestic
system (parameter 2) will be turned OFF
and the display will show “
dOFF
”.
Press and hold “-” button to turn the
domestic system back ON, the display
will show “d” followed by domestic set
point temperature (parameter 1)
NOTICE
STANDBY, no demand for heat
Fan prepurge or post purge cycle
Ignition sequence
Burner ON for space heating (CH)
Burner ON for domestic hot water (DHW)
Pre-check for air flow prior to prepurge cycle
Burner OFF due to reaching temperature setpoint
Domestic hot water (DHW) post pump cycle
Space Heating (CH) post pump cycle
Burner blocked:
Supply temperature too high (202 F) . Burner
will remain OFF until temperature drops
below 200 F
Return temperature too high (202 F). Burner
will remain OFF until temperature drops
below 200 F
Return temperature is higher than
supply temperature. Burner will remain OFF
until corrected.
Supply temperature increased too quickly.
Burner will remain OFF for a 10 minute period.
Burner will recycle, increasing waiting period 1
minute for a max. 15 minutes
Factory supplied LWCO device or
external limit (terminals 15 & 16) is OPEN.
Burner off for 150 seconds, auto reset.
0
1
1
8
0
1
8
0
1
8
0
1
8
0
1
8
0
1
8
0
1
8
0
1
8
0
1
8
0
1
8
0
2
3
4
5
6
7
8
9
1
8
b
1
9
b
2
4
b
2
5
b
2
6
b
2
Display
Boiler function
No blower signal
Blower signal present with no demand, Burner
will remain OFF until condition terminates
Temperature difference between the supply and
return is more than 72 F. Burner will remain OFF
for 150 seconds. Burner will recycle increasing
wating period 1 minute for a max. 20 cycle.
Flue temperature sensor is short-circuited.
Burner OFF until corrected
Flue temperature senor is “open” Burner OFF
until corrected.
Flue temperature greater than 240 F but less
than 250 F. Burner off for 150 seconds
Wait for the blower to start
8
b
2
2
9
b
3
0
b
35
b
4
0
b
Indirect water heater temperature sensor is
short-circuited. Burner OFF until corrected.
Indirect water heater temperature sensor is
“open” or disconnected. Burner OFF until
corrected.
3
3
b
38
b
5
2
b
6
5
b
Power frequency deviation
1
1 6
b
Flame current signal lost
1
8
b
1
Standby Mode Display
Test function: Burner on, high fire mode
Test function: Burner on, low fire mode
180
180
H
L
Display
Boiler function
Start-Up Procedures
43