7.2. Initiating Emergency Broadcasts by Fire Alarm System
If the broadcast system is connected to an automatic fire alarm system, then whenever a fire is detected, the
Fire indicator will illuminate and the FS-7000EV's pre-recorded evacuation announcements will commence
automatically. Operation procedures following the start of such emergency announcements are as follows.
[Buttons and keys used for operation]
[FS-7000CP]
[FS-7010CP]
[FS-7000EV]
Emergency
Reset Button
Fire Indicator
Evacuation
Announcement Button
Evacuation Announcement
Indicator
False Alarm
Announcement Button
False Alarm
Announcement Indicator
Talk Switch
CP Microphone
Zone Selector Keys
Zone Indicators
Zone Selector Keys
Zone Indicators
Using the Zone selector keys on the FS-7000CP and FS-7010CP, select broadcast areas other than
those automatically selected by the fire alarm system.
The appropriate Zone indicators will illuminate.
Broadcast using the microphone on the FS-7000CP.
Make the desired announcement while pressing the Talk switch of the microphone.
Announcements made using the microphone will override any pre-recorded voice alarm broadcasts being
made via the FS-7000EV. These pre-recorded messages will resume once the microphone announcement
has finished.
Broadcasting announcements via microphone
Manually selecting broadcast areas