beautypg.com

Specialty Concepts SC1 User Manual

Page 17

background image

LOAD DISCONNECT CIRCUIT NOT OPERATING CORRECTLY

LOADS ALWAYS DISCONNECTED, LVD LIGHT ON, EVEN WHEN BATTERY VOLTAGE IS
HIGH

See General Note #6 above: No voltage at the BATTERY VOLTAGE SENSE terminals tells

the controller that the battery voltage is low and loads need to be disconnected. Install a
connection from the battery to "BATTERY VOLTAGE SENSE" terminals to resolve.

LOADS DISCONNECTED TOO SOON OR NOT RECONNECTING

See General Note #6 above: The battery may not be reaching the reconnect voltage set-point.
See General Note #12 and #14 above: A poor connection between the controller and the

battery results in a voltage drop when heavy loads are turned on that disappears when the
loads are turned off. The heavier the loads are, the larger the voltage drop will be. This
voltage drop results in the controller seeing a lower voltage than what the battery voltage
actually is.

LOADS NOT DISCONNECTING ON LOW VOLTAGE, LVD LIGHT OFF

Check the position of the "LVD" switch. If the switch is in the "NO LVD" position the load will

not be disconnected.

LOADS ALWAYS DISCONNECTED, LVD LIGHT OFF, BATTERY VOLTAGE IS HIGH

Check the load circuit breaker on the front of the controller. If the breaker is tripped, the load

will not operate.