Slant/Fin Gas Conversion Field User Manual
Page 16

16
Elevation - Feet
V-60 thru V-180
Sentry S-60 thru
S-150 & SX-150 thru
SX-210
TABLE 1
ORIFICE SIZE TABLE
SENTRY AND SENTINEL SERIES
VICTORY SERIES
GALAXY SERIES
2000
3000
4000
5000
6000
7000
8000
9000
10000
Natural
47
48
48
49
49
49
50
50
51
51
Propane
56
56
56
57
57
57
58
59
59
60
Natural
50
51
51
51
51
52
52
52
53
53
Propane
57
58
59
59
60
60
61
62
63
63
All Sentinel models and
Sentry S-34
Boiler
Model
Gas
Type
Orifice Sizes for High Altitudes
Includes 4% Reduction for Each 1000 Feet
Elevation - Feet
Orifice
Size
for
Sea
Level*
2000
3000
4000
5000
6000
7000
8000
9000
10000
Natural
48
49
50
50
50
51
51
52
52
52
Propane
56
56
56
57
57
57
58
59
59
6
Natural
50
51
51
51
52
52
52
52
53
53
Propane
57
58
59
59
60
60
61
62
63
63
V-33
Boiler
Model
Gas
Type
Orifice Sizes for High Altitudes
Includes 4% Reduction for Each 1000 Feet
Elevation - Feet
Orifice
Size
for
Sea
Level*
Orifice
Size
for
Sea
Level*
Gas
Type
Orifice Sizes for High Altitudes
Includes 4% Reduction for Each 1000 Feet
Boiler
Model
*
Orifice indicated for sea level above are factory installed in boiler unless
otherwise specified by the local authority.
See page 19 for burner input adjustment.
** For L.P. Propane consult factory.
Natural
49
50
50
50
51
51
51
52
52
52
Propane
57
58
59
59
60
60
61
62
63
63
2000
3000
4000
5000
6000
7000
8000
9000
10000
GG/GX Except
Natural
42
43
43
43
43
44
44
45
46
47
GG-399H & GG-350H
Propane
54
54
55
55
55
55
55
56
56
56
GG-399H
Natural
40
41
42
42
42
43
43
44
44
45
Propane
53
54
54
54
54
54
54
55
55
55
GXH-105
Natural
44
45
45
45
46
47
47
48
48
49
through 275
Propane
54
54
55
55
55
55
55
56
56
56
GXH-300
Natural
43
44
44
44
45
45
46
47
47
48
Propane
54
54
55
55
55
55
55
56
56
56
GXH-300H
Natural **
42
43
43
43
43
44
45
45
46
47
Gas Only
GXHA
Natural
45
46
47
47
47
48
48
49
49
50
Gas Only
55
55
55
55
56
56
56
56
56
57
VSP, VSPH, VH & VHS
VICTORY II - VHL, VHLS Series (Under 2000 Ft. Only)
Natural
49
Propane
57
VHL, VHLS
Boiler
Model
Gas
Type
Orifice
Size
for
Sea
Level*
SENTINEL SERIES
2000
3000
4000
5000
6000
7000
8000
9000
10000
Natural
47
48
48
49
49
49
50
50
51
51
Propane
56
56
56
57
57
57
58
59
59
60
Sentinel
Boiler
Model
Gas
Type
Orifice Sizes for High Altitudes
Includes 4% Reduction for Each 1000 Feet
Elevation - Feet
Orifice
Size
for
Sea
Level*