CHS Series CHS 300-399 Common Venting
│
Slant Fin Corp.
5
Table 2-3 Acceptable CHS Common Vent and Termination Parts
1
DESCRIPTION
PART No.
COMMENTS
IMAGE
Elbow 6”
2
818 205 (45° Elbow)
818 206 (87 ° Elbow)
-
Straight Pipe Length 6”
3
818 194 (6” x 12”)
818 195 (6” x 24”)
818 196 (6” x 36”)
818 197 (6” x 72”)
-
Connector Ring 6”
4
818 198
Mandatory at every
connection.
Support Clamps 6”
5
818 199
Mandatory every 75” spaced
on vertical runs and every
40” on horizontal runs.
Bird Screen PPs-UV 6”
818 200
PPs-UV Components must
be used for the vent
termination or any area
where the venting is exposed
to sunlight.
Note: Only Centrotherm –
InnoFlue PPs-UV parts are
approved for terminating the
Common Vent System.
End Pipe PPs-UV
818 201 (6” x 20”)
818 202 (6” x 39”)
Elbow PPs-UV 6”
818 203 (87° Elbow)
Elbow PPs-UV 6”
818 204 (45 ° Elbow)
Straight Vent Length
PPs-UV
818 207 (6” x 26.5”)
Notes:
1
With the exception of the CHS Common Venting, the installer is responsible for supplying all the required venting components;
including pipe lengths, termination, Connector Rings, and Support Clamps.
2
When determining the maximum vent lengths each 6” diameter Elbow (87° and 45°) are equivalent to 5 feet of pipe length.
3
The total maximum equivalent vent length for each Exhaust and Air-Inlet is 100 feet.
4
Connector Rings are required on every connection.
5
Support Clamps are required every 75” for vertical runs and every 40” for horizontal runs.
Consult Centrotherm – InnoFlue Eco Systems (1-877-434-3432 o