SilentKnight SK-Relaymon-2 Dual Monitor Module with 2 Relay Outputs User Manual
Page 2
WARNING
All relay switch contacts are shipped in the standby (open) state, but may have transferred to the activated (closed) state during shipping. To ensure that the
switch contacts are in their correct state, modules must be made to communicate with the panel before connecting circuits controlled by the module.
47K EOL
RESISTOR
ELR-47K
47K EOL
RESISTOR
ELR-47K
(-)
(+)
(-)
(+)
FROM PANEL OR
PREVIOUS DEVICE
(-)
(+)
TO NEXT
DEVICE
ANY NUMBER OF UL LISTED CONTACT
CLOSURE DEVICES MAY BE USED. THE
RELAY IS PROGRAMMABLE, E.G. IT WILL
OPERATE FOR ANY SIGNAL FOR WHICH THE
SYSTEM IS PROGRAMMED. DO NOT MIX FIRE
ALARM INITIATING, SUPERVISORY, OR
SECURITY DEVICES ON THE SAME MODULE.
IDC TERMINALS ARE SUPERVISED AND POWER LIMITED
INITIATING DEVICE CIRCUIT (IDC) - NFPA STYLE B
POWER LIMITED: 450µA MAX. @ 10.2 VDC MAX
INSTALL CONTACT CLOSURE DEVICES PER
MANUFACTURER’S INSTALLATION INSTRUCTIONS.
*NOTE: ANY FAULT IN THE POWER SUPPLY IS LIMITED TO THAT
ZONE AND DOES NOT RESULT IN A FAULT IN A SEPARATE ZONE.
IF ANY WIRING TO TERMINALS 7 -12 IS NONPOWER LIMITED,
THE EA-CB BARRIER IS REQUIRED. THE EA-CB INCLUDES A
NONPOWER LIMITED LABEL, WHICH MUST BE PLACED OVER
THE POWER LIMITED TERMINAL INFORMATION ON THE
NAMEPLATE LABEL.
CONNECT MODULES TO LISTED COMPAT-
IBLE CONTROL PANELS ONLY
SIGNAL LINE CIRCUIT (SLC)
32 VDC MAX.
TWISTED PAIR
IS RECOMMENDED
fIgURE 3. TYpICAL 2-WIRE INITIATINg CIRCUIT CONfIgURATION, NfpA STYLE B:
C1051-07
SK-460-019 2 I56-3735-000
©2011 Honeywell International, Inc.
fIgURE 1A. DISABLINg OUTpUT #2 AND INpUT #2
MOUNTINg
The module mounts directly to 4-inch square electrical boxes (see Figure 2).
The box must have a minimum depth of 2
1
/
8
inches. Surface mounted electri-
cal boxes (SMB500) are available from System Sensor. The module can also
mount to the DNR(W) duct housing.
fIgURE 2. MODULE MOUNTINg:
ISOLATED
QUADRANT
C1081-00
C01080-01
fIgURE 1. CONTROLS AND INDICATORS:
C0917-05