SilentKnight SK-Relay Addressable Relay Module User Manual

Page 2

background image

SK-470-001

2

I56-3438-001

©2009 Honeywell International Inc.

Relay Contact Ratings:

CURRENT RATING

MAXIMUM VOLTAGE

LOAD DESCRIPTION

APPLICATION

3 A

30 VDC

Resistive

Non-coded

2 A

30 VDC

Resistive

Coded

.9 A

110 VDC

Resistive

Non-coded

.9 A

125 VDC

Resistive

Non-coded

.5 A

30 VDC

Inductive (L/R=5ms)

Coded

1 A

30 VDC

Inductive (L/R=2ms)

Coded

.3 A

125 VAC

Inductive (PF=.35)

Non-coded

1.5 A

25 VAC

Inductive (PF = .35)

Non-coded

.7 A

70.7 VAC

Inductive (PF=.35)

Non-coded

2 A

25 VAC

Inductive (PF=.35)

Non-coded

WARNING

All relay switch contacts are shipped in the standby state (open) state, but may have transferred to the activated (closed) state during shipping. To ensure that
the switch contacts are in their correct state, modules must be made to communicate with the panel before connecting circuits controlled by the module.

fIgURE 3. RELAy MODULE wIRINg DIAgRAM:

MODULE

FROM PANEL OR

(+)

(–)

TO NEXT

(+)

(–)

DEVICE

(+)

(–)

CONTROL

CONNECT MODULES TO LISTED COMPATIBLE

RELAY COMMON 1

RELAY COMMON 2

NORMALLY CLOSED 1

NORMALLY OPEN 2

NORMALLY CLOSED 2

MODULE DOES NOT SUPERVISE CONTROLLED CIRCUITS

NORMALLY OPEN 1

CONTROL PANELS ONLY

PREVIOUS DEVICE

SIGNAL LINE CIRCUIT (SLC)

32 VDC MAX.

TWISTED PAIR

IS RECOMMENDED

UNUSED

*NOTE: ANY FAULT IN THE POWER SUPPLY IS LIMITED TO THAT ZONE AND DOES NOT RESULT IN A FAULT IN A SEPARATE ZONE.

IF ANY WIRING TO TERMINALS 4 – 10 IS NONPOWER

LIMITED, THE CB500 BARRIER IS REQUIRED. THE CB500

INCLUDES A NONPOWER LIMITED LABEL, WHICH MUST

BE PLACED OVER THE POWER LIMITED TERMINAL

INFORMATION ON THE NAMEPLATE LABEL.

C0946-00