beautypg.com

SilentKnight SK-Monitor Addressable Input Monitor Module User Manual

Sk-monitor module

background image

SpecificationS
Normal Operating Voltage:

15 to 32 VDC

Maximum Current Draw:

5.0 mA (LED on)

Average Operating Current:

375µA (group poll), 350 µA (direct poll), 600 µAmps (communication, IDC shorted)

EOL Resistance:

47K Ohms

Max. IDC wiring resistance:

1,500 Ohms

Maximum IDC Voltage:

11 Volts

Maximum IDC Current:

450µA

Temperature Range:

32°F to 120°F (0°C to 49°C)

Humidity:

10% to 93% Non-condensing

Dimensions:

4

1

2

˝ H x 4˝ W x 1

1

4

˝ D (Mounts to a 4˝ square by 2

1

8

˝ deep box.)

Accessories:

SMB500 Electrical Box

Before inStalling
This information is included as a quick reference installation guide. Refer to
the control panel installation manual for detailed system information. If the
modules will be installed in an existing operational system, inform the opera-
tor and local authority that the system will be temporarily out of service. Dis-
connect power to the control panel before installing the modules.

NOTICE: This manual should be left with the owner/user of this equipment.
general DeScription
The SK-Monitor Module is intended for use in intelligent, two-wire systems,
where the individual address of each module is selected using the built-in
rotary switches. It provides either a Class A or Class B fault tolerant initiating
device circuit (IDC) for normally open contact fire alarm and supervisory de-
vices, or either normally open or normally closed security devices. The mod-
ule has a panel controlled LED indicator.
compatiBility requirementS
To ensure proper operation, this module shall be connected to a compatible
Silent Knight system control panel (list available from Silent Knight).
figure 1. controlS anD inDicatorS:

C1067-00

mounting
The SK-Monitor mounts directly to 4-inch square electrical boxes (see Figure
2). The box must have a minimum depth of 2

1

8

inches. Surface mounted elec-

trical boxes (SMB500) are available from Silent Knight.

inStallation anD maintenance inStructionS

SK-460-013

1

I56-3442-000

SK-monitor module

figure 2. moDule mounting:
NOTE: For UL Listed security installations, the SK-Monitor must be mounted
within the control panel enclosure.

ISOLATED

QUADRANT

C1066-00

Wiring
NOTE: All wiring must conform to applicable local codes, ordinances, and
regulations. This module is intended for power limited wiring only.

1. Install module wiring in accordance with the job drawings and appropri-

ate wiring diagrams.

2. Set the address on the module per job drawings.
3. Secure module to electrical box (supplied by installer), as shown in Figure 2.

I56-3442-000

7550 Meridian Circle, Maple Grove, MN 55369-4927

763-493-6455; 800-328-0103 Fax: 763-493-6475

http://www.silentknight.com