SilentKnight SK-Acclimate / SK-Photo / SK-Photo-T Addressable Photoelectric Smoke Detector w/Thermal User Manual

Installation and maintenance instructions

background image

This sensor must be installed in compliance with the control panel system
installation manual. The installation must meet the requirements of the Au-
thority Having Jurisdiction (AHJ). Sensors offer maximum performance when
installed in compliance with the National Fire Protection Association (NFPA);
see NFPA 72.
GENERAL DESCRIPTION
Models SK-Photo, SK-Photo-T and SK-Acclimate are plug-in type smoke sen-
sors that combine a photoelectronic sensing chamber with addressable-analog
communications. The sensors transmit an analog representation of smoke
density over a communication line to a control panel. Rotary decade switches
are provided for setting the sensor’s address.

Two LEDs on the sensor are controlled by the panel to indicate sensor status. An
output is provided for connection to an optional remote LED annunciator (P/N
RA400Z/RA100Z). Models SK-Acclimate and SK-Photo-T combines a photoelec-
tronic sensing chamber and 135°F (57.2°C) fixed temperature heat detector.

Please refer to the operation manual for the UL listed control unit for specific
operation of the SK-Photo, SK-Photo-T and SK-Acclimate.

The SK-Photo, SK-Photo-T and SK-Acclimate require compatible addressable
communications to function properly. Connect these sensors to listed-compat-
ible control panels only.
SPACING
Silent Knight recommends spacing sensors in compliance with NFPA 72. In
low air flow applications with smooth ceilings, space sensors 30 feet apart. For
specific information regarding sensor spacing, placement, and special applica-
tions, refer to NFPA 72.

Duct Applications: SK-Photo and SK-Photo-T are listed for use in ducts.

NOTE: These products are not listed for use inside duct smoke detectors.
WIRING GUIDE
All wiring must be installed in compliance with the National Electrical Code,
applicable local codes, and any special requirements of the Authority Having
Jurisdiction. Proper wire gauges should be used. The installation wires should
be color-coded to limit wiring mistakes and ease system troubleshooting. Im-
proper connections will prevent a system from responding properly in the
event of a fire.

Remove power from the communication line before installing sensors.

1. Wire the sensor base (supplied separately) per the wiring diagram, Figure 1.
2. Set the desired address on the sensor address switches, see Figure 2.
3. Install the sensor into the sensor base. Push the sensor into the base

while turning it clockwise to secure it in place.

4. After all sensors have been installed, apply power to the control unit and

activate the communication line.

5. Test the sensor(s) as described in the TESTING section of this manual.

CAUTION

Dust covers provide limited protection against airborne dust particles during
shipping. Dust covers must be removed before the sensors can sense smoke.
Remove sensors prior to heavy remodeling or construction.

FIGURE 1. WIRING DIAGRAm:

3

2

1

3

2

1

+

+

+

REMOTE ANNUNCIATOR

CAUTION: DO NOT LOOP WIRE

UNDER TERMINAL 1 OR 2.

BREAK WIRE RUN TO PROVIDE

SUPERVISION OF CONNECTIONS.

UL

LISTED COM

P

A

TIBLE

CONTROL

P

ANEL

OPTIONAL RETURN LOOP

C0100-01

FIGURE 2. ROTARy ADDRESS SWITChES:

TENS

ONES

9

10

11

12

13

14

15

8

7

6

5

4

3

2

1 0

9

8

7

6

5

4

3

2

1 0

C0162-00

TAmPER-RESISTANCE
Models SK-Photo, SK-Photo-T and SK-Acclimate include a tamper-resistant ca-
pability that prevents their removal from the bracket without the use of a tool.
Refer to the base manual for details on making use of this capability.
TESTING
Before testing, notify the proper authorities that the system is undergoing
maintenance, and will temporarily be out of service. Disable the system to
prevent unwanted alarms.

All sensors must be tested after installation and periodically thereafter. Test-
ing methods must satisfy the Authority Having Jurisdiction (AHJ). Sensors
offer maximum performance when tested and maintained in compliance with
NFPA 72.

The sensor can be tested in the following ways:
A. Functional: Magnet Test (P/N M02-04-01 or M02-09-00)

This sensor can be functionally tested with a test magnet. The test mag-
net electronically simulates smoke in the sensing chamber, testing the
sensor electronics and connections to the control panel.

SK-400-004

1

I56-3426-001R

I56-3426-00

1R

INSTALLATION AND mAINTENANCE INSTRUCTIONS

SK-Photo, SK-Photo-T and SK-Acclimate
Intelligent Photoelectric Smoke Sensors

SPECIFICATIONS
Operating Voltage Range:

15 to 32 VDC

Standby Current:

300µA @ 24 VDC Maximum

Alarm Current (LED on):

6.5 mA @ 24 VDC

Operating Humidity Range:

10% to 93% Relative Humidity, Non-condensing

Operating Temperature Range:

32°F to 120°F (0°C to 49°C), SK-Photo; 32°F to 100°F (0°C to 38°C), SK-Photo-T and SK-Acclimate

Height:

2.0˝ (51mm) installed in B210LP Base

Diameter:

6.1˝ (155 mm) installed in B210LP Base; 4.1˝ (104 mm) installed in B501 Base

Weight:

5.2 oz. (147 g)

12 Clintonville Road, Northford, CT 06472

203.484.7161; Fax: 203.484.7118

www.silentknight.com