Model SD505-6IB Installation Instructions

2

P/N 151175

7550 Meridian Circle
Maple Grove, MN 55369-4927
612-493-6455
800-328-0103
Fax: 612-493-6475
© 2000 Silent Knight
P/N 151175B, 12/00

Wiring the SD505-6IB

Note: Installation and wiring of this device must be done

in accordance with NFPA 72 and local ordinances.

Important!: All wiring is supervised and power limited.

Important!: No more than 256 isolator devices (SD505-

LIM or SD505-6IB) can be used on a SLC
loop.

Wiring the SD505-6IB
to the SLC Terminals

The SD505-6IB connections for the SLC loop
internal and external are the same. Wire as
shown in Figure 3 or Figure 4. Notice that “Out
Terminals” wire to “In Terminals”.

Figure 3: Class A (Style 7) Wiring for SLC loop

Figure 4: Class B (Style 4) Wiring for SLC Loop

Mounting the SD505-6IB

The SD505-6IB mounts on a standard single or
double gang electrical switch box.

Follow these steps to mount the SD505-6IB:

1. Mount the extension base using the #8 1-1/2

screws through the extension base mounting
holes. (See Figure 5.)

2. Wire the SLC loop as shown in Figure 3 or

Figure 4.

3. Connect wiring harness to the smoke base as

shown in Figure 5.

4. Plug wiring harness into harness connector.

Refer to Figure 3 and Figure 5.

5. Attach the smoke base (P/N SD505-6AB) to

extension base (P/N 120505) using the #8
1/2”. (See Figure 5.)

Note: Do Not over tighten screws.

Figure 5: SD505-6IB Mounting