Model SD505-LIM Installation Instructions
2
P/N 151125
7550 Meridian Circle
Maple Grove, MN 55369-4927
612-493-6455
800-328-0103
Fax: 612-493-6475
© 1998 Silent Knight
P/N 151125, Rev A, 1/99
Wiring the SD500-LIM
Note: Installation and wiring of this device must be done
in accordance with NFPA 72 and local ordinances.
Important!: All wiring is supervised and power limited.
Important!: No more than 127 isolator devices (LIM or
SD505-6IB) can be used on a SLC loop.
Wiring the SD500-LIM
to the SLC Terminals
The SD500-LIM connections for the SLC loop
internal and external are the same. Wire as
shown in Figure 3 or Figure 4. Notice that “Out
Terminals” wire to “In Terminals”.
Figure 3: LIM Style 7 (Class A) Wiring for SLC loop
Figure 4: LIM Style 4 (Class B) Wiring for SLC Loop
Mounting the SD500-LIM
The SD500-LIM mounts in a standard dual gang
electrical switch box.
Follow these steps to mount the SD500-LIM:
1. Make sure that the SD500-LIM is properly
wired to the control panel. See Figure 3 or
Figure 4.
2. Place the SD500-LIM into the dual gang
electrical switch box. See Figure 5.
3. Mount the SD500-LIM to the dual gang
electrical switch box using two screws as
shown in Figure 5.
4. Insert the two cover plate screws through the
cover plate and screw into the holes on the
SD500-LIM mounting bracket.
Note: Do Not over tighten screws.
Figure 5: SD500-LIM Mounting