beautypg.com

Class b notification configuration, Class a notification configuration, Auxiliary power using flexput™ circuits – SilentKnight SD500-ANM Addressable Notification Module User Manual

Page 2

background image

Model SD500-ANM Installation Instructions

2

7550 Meridian Circle

Maple Grove, MN 55369-4927

763-493-6455 or 800-328-0103

Fax: 763-493-6475

www.silentknight.com

© 2005 Silent Knight PN 151109 Rev C

Class B Notification Configuration

Wire Class B notification appliance circuits to
the SD500-ANM as shown in Figure 2.

Figure 2: SD500-ANM Class B Notification Wiring

Class A Notification Configuration

Wire Class A notification appliance circuits to
the SD500-ANM as shown in Figure 3.

Figure 3: SD500-ANM Class A Notification Wiring

Auxiliary Power Using
Flexput™ Circuits

The SD500-ANM can use aux power from any
24 VDC source. The following describes how to
use the Flexput circuits as the auxiliary power
source:
1. Connect the aux power wires to the Flexput

terminals using “X” terminals as positive
and “O” terminals as negative power. See
Figure 4.

Figure 4: Flexput Auxiliary Power Output

2. Configure the auxiliary power output for

constant output through programming. Refer
to the control panel installation manual for
programming information.

UL listed

4.7 k

Ω

EOL

Model 7628