beautypg.com

Potter EVD-2 User Manual

Page 8

background image

8

EVD-2 • 5401042 • REV N • 6/09

Figure 3. EVD-R Remote Pickup Details

EVD-R Terminal Connections

Terminal Terminal

Description

No.

Name

1

SHIELD

Input Shield Connection from OUT SHIELD of Previous Pickup or End of Line Resistor (See note 1)

2

SIGNAL

Input Sensor Signal from OUT SIGNAL of Previous Pickup or End of Line Resistor (See note 1)

3

REF

Input Reference from OUT REF of Previous Pickup or End of Line Resistor (See note 1)

4

NC

Normally Closed Connection to Safe Contact (See notes 2,3)

5

COM

Common connection to Safe Contact (See notes 2,3)

6

NO

Normally Open Connection to Safe Contact (See notes 2,4)

7

TAMPER

Tamper Connection to Safe Contact (See notes 2,5)

8

TAMPER

Tamper Connection to Safe Contact (See notes 2,5)

9

SPARE

Spare Terminal Block Connection

10

SHIELD

Output Shield Connection to IN SHIELD of Next Pickup or EVD-M SHIELD Connection

11

SIGNAL

Output Sensor Signal to IN SIGNAL of Next Pickup or EVD-M SIGNAL Connection

12

REF

Output Reference to IN REF of Next Pickup or EVD-M REF Connection

Notes
1. Remove all factory installed 10K Ohm, 1% end of line resistors from pins 1-2 and pins 2-3 of all EVD-R's except the last EVD-R remote

pickup in the remote pickup network. See Figures 2b and 4 for details.

2. Connections to optional dry contacts from any UL listed safe contact. See Figure 4 for details.
3. If a safe contact is connected, remove the factory installed jumper from pins 4-5. Pins 4-5 must be NORMALLY CLOSED for the non-alarm state.
4. Pins 5-6 must be NORMALLY OPEN for the non-alarm state.
5. If safe contact tamper is connected, remove the factory installed jumper from pins 7-8. Pins 7-8 must be NORMALLY CLOSED for the

non-tamper state.

6. Pins 1-12 are power limited.

FIELD WIRING

TERMINAL BLOCK

(SEE NOTE 6)

MAGNETICALLY

ACTIVATED TEST

SWITCH

CABLE CLAMP

DWG# 1042-3