Potter RA-7692 User Manual
Page 15
Annunciator Manual • 8910224 • Rev C • 6/09
15
CODE
To change the system user code, press CODE, enter the current user
code followed by 0 + 1, and then enter the new 4-digit user code.
The user code must always be 4 digits.
SPECIAL
Pressing the SPECIAL key and entering the user code initiates the
Fire Drill function.
The Fire Drill sounds the alarm bells and annunciator sounder for
the duration of the Bell Cutoff time. If the Bell Cutoff time is set
to zero (0), the Fire Drill continues until the bells are silenced by
entering a code. No annunciator LEDs are turned on and no reports
are sent to the central station during the Fire Drill.
In the event of a real fire during a fire drill, the system sends a
report to the central station and the LED for any fire-detecting zone
glows red on the RA-7692.
Manual Fire Alarm
To manually initiate a Fire Alarm, press and hold the TEST and CODE
keys simultaneously for about 2 seconds until the alarm sounds.
Resetting Sensors
Use this function to reset smoke detectors after an alarm when the
Fire zone light is flashing in alarm memory.
Enter COMMAND + 4 + 7 to perform a Sensor Reset. The system
resets the smoke detectors and stops the flashing light if the zone
restores to normal.
You can also initiate a Sensor Reset by pressing the RESET
function key followed by your User Code.
Testing the System
It is good practice to test your system at least once each week. This
assures you that the system is working correctly and identifies any
potential problems.
Enter COMMAND + 4 + 1 to perform a system test. The bell rings
for 2 seconds then the battery and communications to the central
station are tested.
You can also initiate a System Test by pressing the TEST function
key followed by your User Code.
User Codes
Use this function to change the current User Code.
Press the CODE key followed by the current User Code. You will
hear one beep if successful. Enter 0 (zero) + 1. Enter the new
4-digit User Code.
2-Button Fire Keys
If your system has a label showing a Flame under the TEST and
CODE keys, the optional Panic key function has been enabled.
Press the two keys over the icon, and hold them down for at least
2 seconds. The system will send a Fire report to the central station.
The annunciator beeps to confirm the Fire key entry.