beautypg.com

LAARS Mighty-Stack TL80-199 - Installation, Operation and Maintenance Instructions User Manual

Page 11

background image

Mighty Stack Water Heater

Page 11

Figure 12. Location of Parts in Control Box.

NOTE: Ensure expansion tank pressure rating is

sufficient to withstand system operational pressure.

1N. Electrical Wiring

1.

Check the voltage, frequency, and phase of the

wiring to the water heater and pump. This unit is

designed to operate on 115V AC, 60 Hz, single

phase. (The controls and switches on this unit

operate on 24V AC. This voltage is produced by

a transformer and draws less than 12 amps.)

2.

A means of switching off 115V AC to the unit is

provided by a 3-position toggle switch on the

control panel (see Figure 12). Additional

switches or connections may be required by local

authority. If there are no local requirements,

follow the latest edition of the National Electrical

Code, ANSI/NFPA 70, in the U.S. In Canada,

follow the latest edition of CSA C22.1 Canadian

Electrical Code, Part 1.

WARNING

The boiler must be electrically grounded. Follow the
requirements of the local authority having
jurisdiction. In the absence of such requirements,
follow the latest edition of the National Electrical
Code ANSI/NFPA 70 in the U.S., or the latest
edition of CSA C22.1 Canadian Electrical Code,
Part 1, in Canada. Do not rely on the gas or water
piping to ground the metal parts of the boiler.
Plastic pipe or dielectric unions may isolate the
boiler electrically. Service and maintenance
personnel who work on or around the boiler may be
standing on wet floors, and could be electrocuted
by an ungrounded boiler.

3.

The 3-position switch is configured as follows:
Middle Position

All power to the unit is shut

off

‘Down’ Position Boiler On, pump in automatic

mode. the pump will shut off

3 minutes after the call for

heat is satisfied.

‘Up’ Position

Boiler On, pump in constant

on mode. The pump will

continue to run after the call

for heat is satisfied.

4.

To make the wiring connections, remove the two

screws which attach the front cover of the

control box.

5.

There are two sets of wires near the top of the

control box. These wires are for connection to

the 115V AC lines. Connect the hot lead from

the 115V power supply to the black wire.

Connect the three white wires to the neutral side

of the 115V line (see Figure 13).

1P. Filling the Storage Water Tank

Caution

Air must be removed from the heater and the tank
before the unit is operated. If this is not done, the
heat exchanger may be damaged.

1.

Open the hot water faucet(s) to allow air to escape.

2.

Open the shut-off valve(s) in the cold water

supply line.

3.

Open the shut-off valve(s) in the hot water

supply line.

4.

Turn off the gas to the unit, but allow the pump

to run for about 15 minutes. This will allow any

remaining air to collect in the top of the tank.

5.

Open the pressure relief valve to remove any

remaining air.

6.

Turn on the gas and check for leaks. Now the

unit is ready to operate.