Out of production – LAARS Mighty Max VW (Sizes 320M - 400M) - Installation, Operation and Maintenance Instructions User Manual
Page 20

Page 20
LAARS Heating Systems
Figure 14. Unfired Venturi Differential Pressure -
Natural Gas.
5.8" WC
Gas
Plenum Tap
Gas
Orifice Tap
Venturi
Inlet Tap
Figure 15. Gas Offset Pressure - Natural Gas.
0.4" WC
Figure 16. Gas Orifice Differential Pressure - Natural Gas.
4.0" WC
a. Unfired Venturi Differential Pressure
NOTE: Turn off the main manual gas valve.
The difference in pressure between the venturi
inlet tap and the gas plenum tap (see Figure 14). This
measurement is taken by connecting the positive side
of the manometer to the venturi inlet tap and
connecting the negative side of the manometer to the
gas plenum tap. This measurement is taken with the
boiler not firing. It is a temporary setting used to start
the boiler and check for air flow problems.
b. Gas Offset Pressure - Natural Gas
The difference in pressure between the venturi
inlet tap and the outlet of the gas regulator (see
Figure 15). This measurement is taken by connecting
the positive side of the manometer to the venturi inlet
tap and connecting the negative side of the manometer
to the gas orifice tap. This measurement is an
indication of the gas to air ratio and must be
performed while the unit is firing.
c. Gas Orifice Differential Pressure -
Natural Gas
This measurement is the pressure drop across the
gas orifice. This measurement is taken by connecting
the positive side of the manometer to the gas orifice
tap and the negative side of the manometer to the gas
plenum tap (see Figure 16). This measurement in
conjunction with the gas orifice size is an indication of
the gas firing rate and must be performed while the
unit is firing.
OUT OF
PRODUCTION