beautypg.com

Out of production – LAARS Mighty Max VW (Sizes 320M - 400M) - Installation, Operation and Maintenance Instructions User Manual

Page 10

background image

Page 10

LAARS Heating Systems

The following requirements must be used for

Non-Category I venting:
1.

Laars specified vent pipe material (Table 6) and

sizes (Table 7).

2.

Pipe insulation and sealing tape.

3.

Routing vent pipe through spaces which, except

for the terminal, remain above 60°F (16°C)

during heater operation.

2.10.3 Horizontal Venting - Non-Category I
When venting is horizontal, or cannot meet the

code requirements for Category I - Blower-Assisted

Vertical Vents, it can develop positive pressure and

must be installed in accordance with this section.

The following requirements must be used for

Horizontal Venting - Non-Category I:
1.

Laars specified vent piping materials

(Table 6) and sizes (Table 7).

2.

Laars side wall vent hood.

3.

Pipe insulation and sealing tape.

4.

Routing vent pipe through spaces which, except

for the terminal, remain above 60°F (16°C)

during heater operation.

2.10.4 Side Wall Vent Terminal

The side wall vent hood must be used when the

heater is vented through a side wall. It provides a

means of installing vent piping through the building

wall, and must be located in accordance with ANSI

Z223.1/NFPA 54 and applicable local codes. In

Canada the installation must be in accordance with

CSA B149.1 and local applicable codes (see Figure 9).

Consider the following when installing the terminal:
1.

Locate the vent terminal so that it will not be

damaged by pedestrians and other traffic, and so

the discharge is not objectionable. The National

Fuel Gas Code requires a through-wall vent

terminal be at least 7 feet (2.1m) above grade if

located at a public walkway.

2.

Locate the vent terminal so that vent gases

cannot be drawn into air conditioning system

inlets. The National Fuel Gas Code requires that

it be at least 6 feet (1.8m) above any such inlet

that is within 10 feet (3m).

3.

Locate the vent terminal so that vent gases

cannot enter the building through doors,

windows, gravity inlets or other openings. The

National Fuel Gas Code requires that it be

located at least 4 feet (1.2m) below, 4 feet (1.2m)

horizontally from, or 3 feet (0.9m) above such

openings.

4.

Locate the vent terminal so that it cannot be

blocked by snow. The National Fuel Gas code

requires that it be at least 12 inches (305mm)

above grade, but the installer may determine it

should be higher depending on local conditions.

5.

Locate the terminal so the vent exhaust does not

settle on building surfaces and other nearby

objects. Vent products may damage such

surfaces or objects. But the actual construction of

the vent terminal and the flow of vent products

must not be altered.

6.

Locate the terminal at least 6 feet (1.8m)

horizontally from any gas or electric metering,

regulating, or relief equipment, or building

opening.

Mighty Max units are Category I fan-assisted

when vented vertically and adhering to all applicable

codes. Mighty Max units are not allowed to be vented

into a common horizontal vent system, unless a

properly-sized vent fan is used, and the common vent

system is properly designed by the vent fan

manufacturer or a qualified engineer.

When common venting Mighty Max fan-assisted

heaters with other appliances through one shared

vertical duct called a “common vent”, special care

must be taken by the installer to ensure safe operation.

In the event that the common vent is blocked, it is

possible, especially for fan-assisted devices, to vent

backwards through non-operating appliances sharing

the vent, allowing combustion products to infiltrate

occupied spaces. If the appliances are allowed to

operate in this condition, serious injury or death may

occur.

WARNING

Operation of appliances with a blocked common
vent may lead to serious injury or death. Safety
devices must be implemented to prevent blocked
common vent operation. If safe operation of all
appliances connected to a common vent cannot be
assured, including prevention of spillage of flue
gasses into living spaces, common venting should
not be applied, and appliances should each be
vented separately.

Term

Description

Pipe

Must comply with UL Standard 1738
such as type 29-4C stainless steel

Joint Sealing

Follow vent manufacturer's
instructions

Insulation

Recommended, but not required,
minimum R5 with protective cover

Table 6. Required Horizontal Venting Material.

OUT OF

PRODUCTION