LAARS Pennant PNCP - Install and Operating Manual User Manual
Page 15

Pennant Pool Heater
Page 15
changing the dLS parameter. After scrolling through
the parameters until dLS is displayed, press the enter
button. The setpoint will be displayed. Press the up
arrow or down arrow buttons until the desired setpoint
is displayed. Press the enter button and the setpoint
will be activated. The display will return to indicating
the present pool loop temperature.
The boiler operating temperature is set by
changing the bsp parameter. After scrolling through
the parameters until bsp is displayed, press the enter
button. The setpoint will be displayed. Press the up
arrow or down arrow buttons until the desired setpoint
is displayed. Press the enter button and the setpoint
will be activated. The display will then return to
indicating the pool loop temperature.
SINGLE
TWO CIRCUIT
SIZE
CIRCUIT
HEATER PUMP
500
20
15
15
750
20
15
15
1000
(TACO) 20 / (B&G) 30 20
15
1250
30
25
15
1500
30
25
15
1750
25
20
2000
25
20
Table 8. Electrical Data (Amps).
Figure 9. Typical Control Panel.
Figure 8. Pool Heater Controller.
The last parameter that may be adjusted is Pd,
the pump off delay. After again scrolling through the
parameters until Pd is displayed, press the enter button.
The pump delay time will be displayed. The pump off
delay may be set between 0.1 and 10 minutes. Press
the up arrow or down arrow buttons until the desired
setpoint is displayed. Press the enter button and the
setpoint will be activated. The display will again return
to indicating the present pool loop temperature.
By depressing the upper left hand button at
any time during the programming, the menu may be
returned to the beginning.
5.3.3 Setpoint - LSP
The setpoint is the desired temperature around
which the heater will control (desired pool temp-
erature). It is adjustable between 60° F and 104° F.