COOLING-ONLY PROCEDURE

NOTE:

If superheat- or subcooling-charging conditions are not

favorable, charge must be weighed in accordance with unit-rating
plate ±0.6 oz/ft of 3/8-in. liquid line above or below 15 ft
respectively.

EXAMPLE:

To calculate additional charge required for a 25-ft line set:

25 ft – 15 ft = 10 ft X 0.6 oz/ft = 6 oz of additional charge

HEATING CHECK-CHART PROCEDURE

To check system operation during heating cycle, refer to the
Heating Check Chart on outdoor unit. This chart indicates whether
a correct relationship exists between system operating pressure and
air temperature entering indoor and outdoor units. If pressure and
temperature do not match on chart, system-refrigerant charge may
not be correct. Do not use chart to adjust refrigerant charge.

NOTE:

When charging is necessary during heating season,

charge must be weighed in accordance with unit rating plate ±0.6
oz/ft of 3/8-in. liquid line above or below 15 ft respectively.

Step 14—Final Checks

IMPORTANT:

Before leaving job, be sure to do the following:

1. Securely fasten all panels and covers.

2. Tighten service valve-stem caps to 1/12-turn past finger-tight.

3. Leave User’s Manual with owner. Explain system operation

and periodic maintenance requirements outlined in manual.

4. Fill out Dealer Installation Checklist and place in customer

file.

Fig. 7—Phase-Monitor Control

Table 2—Phase-Monitor LED Indicators

LED

STATUS

OFF

No call for compressor

operation

FLASHING

Reversed phase

ON

Normal

A00010