50pg03 – Carrier 50PG03-07 User Manual
Page 14

14
Table 2 -- Electrical Data -- Units Without Optional Convenience Outlet (cont)
UNIT
50PG
NOMINAL
POWER SUPPLY
Volts-Ph-Hz
VOLTAGE
RANGE
COMPRESSOR
OFM
FLA
POWER
EXHAUST
FLA
IFM
TYPE
IFM
FLA
ELECTRIC HEAT
POWER SUPPLY
DISCONNECT
SIZE
Min
Max
RLA
LRA
FLA
Nominal
kW*
MCA
MOCP†
FLA
LRA
05
(cont)
460-3-60
414
506
7.1
46
0.5
—
Low
2.1
—
—
11.5
15
11
53
5.8
5.0
11.5
15
11
53
8.7
7.5
13.5
15
12
53
11.5
10.0
17.0
20
16
53
17.3
15.0
24.3
25
22
53
23.1
20.0
31.5
35
29
53
High
2.6
—
—
12.0
15
12
62
5.8
5.0
12.0
15
12
62
8.7
7.5
14.1
15
13
62
11.5
10.0
17.6
20
16
62
17.3
15.0
24.9
25
23
62
23.1
20.0
32.1
35
30
62
0.6
Low
2.1
—
—
12.1
15
12
54
5.8
5.0
12.1
15
12
54
8.7
7.5
14.3
15
13
54
11.5
10.0
17.8
20
16
54
17.3
15.0
25.0
30
23
54
23.1
20.0
32.3
35
30
54
High
2.6
—
—
12.6
15
12
63
5.8
5.0
12.6
15
12
63
8.7
7.5
14.9
15
14
63
11.5
10.0
18.4
20
17
63
17.3
15.0
25.6
30
24
63
23.1
20.0
32.9
35
30
63
575-3-60
518
633
5.1
34
0.5
—
Low
2.1
—
—
9.0
15
9
40
9.2
10.0
14.1
15
13
40
13.9
15.0
20.0
25
18
40
18.5
20.0
25.8
30
24
40
High
2.0
—
—
8.9
15
9
46
9.2
10.0
14.0
15
13
46
13.9
15.0
19.9
20
18
46
18.5
20.0
25.6
30
24
46
1.4
Low
2.1
—
—
10.4
15
10
42
9.2
10.0
15.9
20
15
42
13.9
15.0
21.8
25
20
42
18.5
20.0
27.5
30
25
42
High
2.0
—
—
10.3
15
10
48
9.2
10.0
15.8
20
14
48
13.9
15.0
21.6
25
20
48
18.5
20.0
27.4
30
25
48
06
208/230-1-60
187
253
26.9
145
1.5
—
Low
4.9
—
—
40.0/ 40.0
45/ 45
38/38 160/160
17.3/ 20.0
3.8/ 5.0
40.0/ 40.0
45/ 45
38/38 160/160
26.0/ 30.0
5.6/ 7.5
40.0/ 43.6
45/ 45
38/40 160/160
34.7/ 40.0
7.5/10.0
49.5/ 56.1
50/ 60
46/52 160/160
52.0/ 60.0
11.3/15.0
71.1/ 81.1
80/ 90
65/75 160/160
69.3/ 80.0
15.0/20.0
92.8/106.1 100/110
85/98 160/160
86.7/100.0
18.8/25.0
114.5/131.1 125/150 105/121 160/160
High
7.0
—
—
42.1/ 42.1
45/ 45
41/41 185/185
17.3/ 20.0
3.8/ 5.0
42.1/ 42.1
45/ 45
41/41 185/185
26.0/ 30.0
5.6/ 7.5
42.1/ 46.3
45/ 50
41/43 185/185
34.7/ 40.0
7.5/10.0
52.1/ 58.8
60/ 60
48/54 185/185
52.0/ 60.0
11.3/15.0
73.8/ 83.8
80/ 90
68/77 185/185
69.3/ 80.0
15.0/20.0
95.4/108.8 100/110
88/100 185/185
86.7/100.0
18.8/25.0
117.1/133.8 125/150 108/123 185/185
1.4
Low
4.9
—
—
41.4/ 41.4
45/ 45
40/40 162/162
17.3/ 20.0
3.8/ 5.0
41.4/ 41.4
45/ 45
40/40 162/162
26.0/ 30.0
5.6/ 7.5
41.4/ 45.4
45/ 50
40/42 162/162
34.7/ 40.0
7.5/10.0
51.3/ 57.9
60/ 60
47/53 162/162
52.0/ 60.0
11.3/15.0
72.9/ 82.9
80/ 90
67/76 162/162
69.3/ 80.0
15.0/20.0
94.5/107.9 100/110
87/99 162/162
86.7/100.0
18.8/25.0
116.3/132.9 125/150 107/122 162/162
High
7.0
—
—
43.5/ 43.5
50/ 50
42/42 187/187
17.3/ 20.0
3.8/ 5.0
43.5/ 43.5
50/ 50
42/42 187/187
26.0/ 30.0
5.6/ 7.5
43.5/ 48.0
50/ 50
42/44 187/187
34.7/ 40.0
7.5/10.0
53.9/ 60.5
60/ 70
50/56 187/187
52.0/ 60.0
11.3/15.0
75.5/ 85.5
80/ 90
69/79 187/187
69.3/ 80.0
15.0/20.0
97.1/110.5 100/125
89/102 187/187
86.7/100.0
18.8/25.0
118.9/135.5 125/150 109/125 187/187
LEGEND
FLA
--- Full Load Amps
HACR --- Heating, Air Conditioning and Refrigeration
IFM
--- Indoor (Evaporator) Fan Motor
LRA
--- Locked Rotor Amps
MCA --- Minimum Circuit Amps
MOCP --- Maximum Overcurrent Protection
NEC
--- National Electrical Code
OFM --- Outdoor (Condenser) Fan Motor
RLA
--- Rated Load Amps
*Heater capacity (kW) is based on heater voltage of 208v, 240v, 480v, or 600v. If power
distribution voltage to unit varies from rated heater voltage, heater kW will vary accord-
ingly.
{
Fuse or HACR circuit breaker.
NOTES:
1. In compliance with NEC requirements for multimotor and combination load equipment (refer
to NEC Articles 430 and 440), the overcurrent protective device for the unit shall be fuse or
HACR breaker. Canadian units may be fuse or circuit breaker.
2.
Unbalanced 3-Phase Supply Voltage
Never operate a motor where a phase imbalance in supply voltage is greater than 2%. Use
the following formula to determine the percentage of voltage imbalance.
% Voltage Imbalance
= 100 x
max voltage deviation from average voltage
average voltage
Example: Supply voltage is 230---3---60
AB = 224 v
BC = 231 v
AC = 226 v
Average Voltage = 224 + 231 + 226
3
681
3
=
227
=
Determine maximum deviation from average voltage.
(AB) 227 – 224 = 3 v
(BC) 231 – 227 = 4 v
(AC) 227 – 226 = 1 v
Maximum deviation is 4 v.
Determine percent of voltage imbalance.
% Voltage Imbalance
= 100 x
4
227
= 1.76%
This amount of phase imbalance is satisfactory as it is below the maximum allowable 2%.
IMPORTANT: If the supply voltage phase imbalance is more than 2%, contact your local electric
utility company immediately.
50PG03
--