Table 2 -- Electrical Data -- Units Without Optional Convenience Outlet (cont)

UNIT

50PG

NOMINAL

POWER SUPPLY

Volts-Ph-Hz

VOLTAGE

RANGE

COMPRESSOR

OFM

FLA

POWER

EXHAUST

FLA

IFM

TYPE

IFM

FLA

ELECTRIC HEAT

POWER SUPPLY

DISCONNECT

SIZE

Min

Max

RLA

LRA

FLA

Nominal

kW*

MCA

MOCP†

FLA

LRA

05

(cont)

460-3-60

414

506

7.1

46

0.5

Low

2.1

11.5

15

11

53

5.8

5.0

11.5

15

11

53

8.7

7.5

13.5

15

12

53

11.5

10.0

17.0

20

16

53

17.3

15.0

24.3

25

22

53

23.1

20.0

31.5

35

29

53

High

2.6

12.0

15

12

62

5.8

5.0

12.0

15

12

62

8.7

7.5

14.1

15

13

62

11.5

10.0

17.6

20

16

62

17.3

15.0

24.9

25

23

62

23.1

20.0

32.1

35

30

62

0.6

Low

2.1

12.1

15

12

54

5.8

5.0

12.1

15

12

54

8.7

7.5

14.3

15

13

54

11.5

10.0

17.8

20

16

54

17.3

15.0

25.0

30

23

54

23.1

20.0

32.3

35

30

54

High

2.6

12.6

15

12

63

5.8

5.0

12.6

15

12

63

8.7

7.5

14.9

15

14

63

11.5

10.0

18.4

20

17

63

17.3

15.0

25.6

30

24

63

23.1

20.0

32.9

35

30

63

575-3-60

518

633

5.1

34

0.5

Low

2.1

9.0

15

9

40

9.2

10.0

14.1

15

13

40

13.9

15.0

20.0

25

18

40

18.5

20.0

25.8

30

24

40

High

2.0

8.9

15

9

46

9.2

10.0

14.0

15

13

46

13.9

15.0

19.9

20

18

46

18.5

20.0

25.6

30

24

46

1.4

Low

2.1

10.4

15

10

42

9.2

10.0

15.9

20

15

42

13.9

15.0

21.8

25

20

42

18.5

20.0

27.5

30

25

42

High

2.0

10.3

15

10

48

9.2

10.0

15.8

20

14

48

13.9

15.0

21.6

25

20

48

18.5

20.0

27.4

30

25

48

06

208/230-1-60

187

253

26.9

145

1.5

Low

4.9

40.0/ 40.0

45/ 45

38/38 160/160

17.3/ 20.0

3.8/ 5.0

40.0/ 40.0

45/ 45

38/38 160/160

26.0/ 30.0

5.6/ 7.5

40.0/ 43.6

45/ 45

38/40 160/160

34.7/ 40.0

7.5/10.0

49.5/ 56.1

50/ 60

46/52 160/160

52.0/ 60.0

11.3/15.0

71.1/ 81.1

80/ 90

65/75 160/160

69.3/ 80.0

15.0/20.0

92.8/106.1 100/110

85/98 160/160

86.7/100.0

18.8/25.0

114.5/131.1 125/150 105/121 160/160

High

7.0

42.1/ 42.1

45/ 45

41/41 185/185

17.3/ 20.0

3.8/ 5.0

42.1/ 42.1

45/ 45

41/41 185/185

26.0/ 30.0

5.6/ 7.5

42.1/ 46.3

45/ 50

41/43 185/185

34.7/ 40.0

7.5/10.0

52.1/ 58.8

60/ 60

48/54 185/185

52.0/ 60.0

11.3/15.0

73.8/ 83.8

80/ 90

68/77 185/185

69.3/ 80.0

15.0/20.0

95.4/108.8 100/110

88/100 185/185

86.7/100.0

18.8/25.0

117.1/133.8 125/150 108/123 185/185

1.4

Low

4.9

41.4/ 41.4

45/ 45

40/40 162/162

17.3/ 20.0

3.8/ 5.0

41.4/ 41.4

45/ 45

40/40 162/162

26.0/ 30.0

5.6/ 7.5

41.4/ 45.4

45/ 50

40/42 162/162

34.7/ 40.0

7.5/10.0

51.3/ 57.9

60/ 60

47/53 162/162

52.0/ 60.0

11.3/15.0

72.9/ 82.9

80/ 90

67/76 162/162

69.3/ 80.0

15.0/20.0

94.5/107.9 100/110

87/99 162/162

86.7/100.0

18.8/25.0

116.3/132.9 125/150 107/122 162/162

High

7.0

43.5/ 43.5

50/ 50

42/42 187/187

17.3/ 20.0

3.8/ 5.0

43.5/ 43.5

50/ 50

42/42 187/187

26.0/ 30.0

5.6/ 7.5

43.5/ 48.0

50/ 50

42/44 187/187

34.7/ 40.0

7.5/10.0

53.9/ 60.5

60/ 70

50/56 187/187

52.0/ 60.0

11.3/15.0

75.5/ 85.5

80/ 90

69/79 187/187

69.3/ 80.0

15.0/20.0

97.1/110.5 100/125

89/102 187/187

86.7/100.0

18.8/25.0

118.9/135.5 125/150 109/125 187/187

LEGEND

FLA

--- Full Load Amps

HACR --- Heating, Air Conditioning and Refrigeration

IFM

--- Indoor (Evaporator) Fan Motor

LRA

--- Locked Rotor Amps

MCA --- Minimum Circuit Amps

MOCP --- Maximum Overcurrent Protection

NEC

--- National Electrical Code

OFM --- Outdoor (Condenser) Fan Motor

RLA

--- Rated Load Amps

*Heater capacity (kW) is based on heater voltage of 208v, 240v, 480v, or 600v. If power

distribution voltage to unit varies from rated heater voltage, heater kW will vary accord-

ingly.
{

Fuse or HACR circuit breaker.

NOTES:

1. In compliance with NEC requirements for multimotor and combination load equipment (refer

to NEC Articles 430 and 440), the overcurrent protective device for the unit shall be fuse or

HACR breaker. Canadian units may be fuse or circuit breaker.

2.

Unbalanced 3-Phase Supply Voltage

Never operate a motor where a phase imbalance in supply voltage is greater than 2%. Use

the following formula to determine the percentage of voltage imbalance.

% Voltage Imbalance

= 100 x

max voltage deviation from average voltage

average voltage

Example: Supply voltage is 230---3---60

AB = 224 v

BC = 231 v

AC = 226 v
Average Voltage = 224 + 231 + 226

3

681

3

=

227

=

Determine maximum deviation from average voltage.

(AB) 227 – 224 = 3 v
(BC) 231 – 227 = 4 v

(AC) 227 – 226 = 1 v
Maximum deviation is 4 v.

Determine percent of voltage imbalance.

% Voltage Imbalance

= 100 x

4

227

= 1.76%

This amount of phase imbalance is satisfactory as it is below the maximum allowable 2%.

IMPORTANT: If the supply voltage phase imbalance is more than 2%, contact your local electric
utility company immediately.

50PG03

--