Central station communication, Specifications, Regulatory information – Interlogix Simon XT REV B Installation Manual User Manual
Page 6: Ul listed installations, 6shflilfdwlrqv, 5hjxodwru\lqirupdwlrq
![background image](/manuals/679362/6/background.png)
1RWH
Refer to specific sensor installation instructions for complete
operation and testing details.
&HQWUDOVWDWLRQFRPPXQLFDWLRQ
After performing sensor tests, check that the system is reporting
alarms successfully to the central station.
7RWHVWFRPPXQLFDWLRQZLWKWKHFHQWUDOVWDWLRQ
1. Call the central station and tell the operator that you will be
testing the system.
2. Arm the system.
3. Test each of the wireless panic buttons and trip at least one
sensor of each type (fire, intrusion, etc.) to verify that the
appropriate alarms are working correctly.
There is a 30 second delay.
4. When you finish testing the system, call the central station to
verify that the alarms were received.
6SHFLILFDWLRQV
Power
9 VAC, 60 Hz, 25 VA transformer minimum
Rechargeable battery: 6.0 VDC, 1.2 Ah lead-acid.
The battery will last 24 hours with no AC and
specified standby load of 250 mA. Maximum
battery charging current is 45 mA. With loss of
AC, panel will continue to operate normally to a
minimum of 5.1 VDC.
Radio frequency
319.5 MHz
Storage temperature -29 to 140ºF (-34 to 60ºC)
Operating
temperature
32 to 120ºF (0 to 49ºC)
Maximum humidity
85% relative humidity, noncondensing
Auxiliary power
Unregulated 5.3 to 12.3 VDC, with a maximum of
250 mA
5HJXODWRU\LQIRUPDWLRQ
8/OLVWHGLQVWDOODWLRQV
Some installation may require configurations dictated by
city/state codes, insurance, or Underwriter’s Laboratories (UL). This
section describes the various component and configuration
listings.
Basic system:
•
Control panel: Backup battery 6 V 1.2 Ah (34-025) (Portalac
model # PE6V1.2)
•
Standard class 2, 9 VAC, 3.34 A power transformer (part 22-
153). Alternate transformer for US installations: MG
Electronics model MGT925, 9 VAC, 25 VA, (part 22-155)
•
Hardwired siren (13-374)
Household burglary alarm system unit (UL 1023), basic system
plus the following:
•
Hardwired magnetic contact (13-068 or 13-071) or wireless
learn mode door/window sensor (60-670)
•
Panel piezo beeps set to on
•
Entry delay set to 45 seconds or less
•
Exit delay set to 60 seconds or less
•
RF time-out set to 24 hours
•
Control panel alarms turned on
•
Auto arm set to on
•
Siren timeout set to 5 minutes or more
•
Trouble beeps set to on
•
RF jam detect set to on
•
Hardwired siren supervision set to on
•
Exit extension set to off
•
Quick exit set to off
Household fire warning system (UL 985), basic system plus the
following:
•
Wireless smoke sensor 60-848-02-95, TX-6010-01-1 learned
into sensor group 26.
•
Panel piezo beeps turned on
•
Control panel alarms set to on
•
Siren timeout set to 4 minutes or more
•
Trouble beeps set to on
•
RF jam detect set to on
•
Hardwired siren supervision set to on
•
Smoke supervision set to on
UL 1023 and 985 24-hour backup:
•
For 24-hour backup, the total current draw for all connected
devices is limited to 240 mA (during normal standby
conditions) using a 1.2 AH battery.
UL 1635 digital alarm communicator system (same as UL 1023
and 985) plus the following settings are in addition to UL 1023 and
985 and are required only if the system is set up for central station
reporting:
•
Phone mod 1 set to 0 or 1
•
Automatic phone test set to 001
•
RF timeout set to 4 hours
•
AC power failure report set to on
•
CPU low battery report set to on
•
Fail to communicate set to on
•
Entry delay plus the dialer delay must not exceed 60 seconds
6 / 8
P/N 466-2398 • REV B • ISS 09JAN13