beautypg.com

Main, Step 1, Step 2 – Carrier 48PG20---28 User Manual

Page 7: Step 3, Step 4, Step 5, Step 6, Step 7

background image

7

LOCK-OUT

TAG

ON

OFF

MAIN

STEP 1

STEP 2

STEP 3

STEP 4

STEP 5

STEP 6

STEP 7

OFF

ON

CONTROL I.D.
LABEL

1/4˝ X .032˝ MALE SPADE
TERMINALS (2) COMMON

SWITCH (SHIPPED IN
“ON” POSITION)

C09578

Fig. 4 -- To Shut Unit Off

Step 1 —

Turn off the unit demand for cooling or heating by

using the Scrolling Marquee. The Scrolling Marquee is located in
the control box at the compressor end of the unit.

a. Push the ESCAPE key until a blank display screen is

shown.

b. Push the DOWN arrow key until the SERVICE TEST

LED is lit.

c. Push the ENTER key. The display will show TEST.

d. Push the ENTER key again. The NO/YES display will

flash.

e. Push the UP or DOWN key to toggle the display to

YES and then push ENTER . The unit will be locked

off from heat, cooling or any operation. The controls
will still function and the display will still operate.

NOTE: A password may be required to change Service Test
values depending on previous settings configured in the unit.
Default password is “1111.”

Step 2 —

Close the external gas pipings manual shut off valve

located outside the unit.

Step 3 —

Turn off the electrical power supply to the unit and

install lockout tag.

Step 4 —

Remove the heat section access panel.

Step 5 —

Turn the control dial on the main gas valve

counterclockwise to the OFF position.

Step 6 —

Replace the heat section access panel.

Step 7 —

If unit is being shut down because of a malfunction,

call your dealer as soon as possible.