Troubleshooting – FloAire Direct Expansion Coil Modules User Manual
Page 14
![background image](/manuals/676142/14/background.png)
14
Troubleshooting
The following table lists causes and corrective actions for possible problems with DX coil modules.
Review this list prior to consulting manufacturer.
Troubleshooting Chart
* Air velocity should be maintained between 200 and 550 FT per Minute through the coil.
Problem
Potential Cause
Corrective Action
Insufficient Cooling
Frozen coil
Reduce refrigerant charge.
Check for proper airflow across
coil.
Charge is low
Add refrigerant charge.
Excessive air flow
Slow blower RPM down.
Contaminated refrigerant
Have refrigerant replaced.
Frozen coil
Reduce refrigerant charge.
Insufficient Airflow
Coil sized too small *
Increase airflow across coil.
Replace module with larger coil.
Overestimation of static pressure
Reduce blower rpm.
Excessive Airflow
Coil sized too large *
Change motor HP.
Slow blower RPM down.
Excessive airflow
Slow blower RPM down.
Water in ductwork
Drip pan full
Check drip pan for obstructions.
Ductwork is not insulated
Check drip pan plumbing for
clogs.
Insulate ductwork to reduce
condensation.