Mac 10, Ledc, 4x4 fan filter unit – Envirco MAC 10 LE-DC User Manual
Page 19: Limted warranty, Testing

MAC 10
®
LEDC
4x4 Fan Filter Unit
19
Innovators in Clean Air Technology | www.envirco.com | Operation & Maintenance
I n s t a l l a t i o n & S e r v i c e M a n u a l
■
Limted Warranty
LIMITED WARRANTY: Unless otherwise expressly stated
in Envirco’s published specifications for the Goods, Envirco
warrants that Goods are free from defects in material and
workmanship, except for services which are warranted to be
performed in a competent and diligent manner in accordance
with any mutually agreed specifications. The foregoing
warranty shall apply for eighteen (18) months from the date
of shipment from Envirco’s facility, except for services for
which the warranty shall apply for ninety (90) days from
the date of performance (the “Warranty Period”). Provided
Buyer informs Envirco in writing of any breach of warranty
prior to the expiration of the applicable Warranty Period,
Envirco shall, as its sole obligation and Buyer’s sole and
exclusive remedy for any breach of this warranty, repair or
replace/re-perform the Goods which gave rise to the breach
or, at Envirco’ option, refund the amounts paid by Buyer
for the Goods which gave rise to the breach. Any repair,
replacement or re-performance by Envirco hereunder shall
not extend the applicable Warranty Period. The parties shall
mutually agree on the specifications of any test to determine
the presence of a defect. Unless otherwise agreed upon by
Envirco in writing, Buyer shall bear the costs of access, de-
installation, re-installation and transportation of Goods to
Envirco and back to Buyer. These warranties and remedies
are conditioned upon (a) the proper storage, installation,
operation, and maintenance of the Goods and conformance
with the proper operation instruction manuals provided by
Envirco or its suppliers or subcontractors, (b) Buyer keeping
proper records of operation and maintenance during the
applicable Warranty Period and providing Envirco access to
those records, and (c) modification or repair of the Goods
only as authorized by Envirco. Envirco does not warrant the
Goods or any repaired or replacement parts against normal
wear and tear or damage caused by misuse, accident, or
use against the instructions of Envirco. Any modification or
repair of any of the Goods not authorized by Envirco shall
render the warranty null and void. EXCEPT AS EXPRESSLY
SET FORTH HEREIN, ENVIRCO MAKES NO OTHER
WARRANTIES, EXPRESS OR IMPLIED, INCLUDING,
BUT NOT LIMITED TO, ANY IMPLIED WARRANTIES
OF MERCHANTABILITY, NON-INFRINGEMENT OR
FITNESS FOR A PARTICULAR PURPOSE WHICH ARE
HEREBY DISCLAIMED TO THE EXTENT PERMITTED BY
APPLICABLE LAW.
■
Testing
Each MAC 10 LEDC filter unit is thoroughly tested at the
factory before shipment. However, because of the “rigors” of
shipping, ENVIRCO encourages its re-test after installation.
ENVIRCO recommends that the customer contact an
independent organization, with technicians trained and
experienced in performance evaluation and maintenance of
clean air equipment.
HEPA filters (Type J) are tested to IEST-RP-00034. ULPA
filters are tested to (Type F) IEST-RP-00034. All filters are UL
900 recognized. Your filters may have special requirements,
please see original engineering specifications for you specific
project.
All units that are airflow tested at Envirco are tested using a
Shortridge Airdata Multimeter 870 with a Velgrid head. The
recommended method of reading is to place one corner of
the Velgrid head 1-1/4” from the corner of the filter face and
then take four reading evenly spaced along the four foot
side, then repeat these reads three additional times. This
gives a total of 16 reading to test the unit. All advertised data
is based on using the Velgrid with 16 readings (256 velocity
points). Envirco recognized the using 16 reading during a
cleanroom start-up may be time consuming and recommends
using 4 Velgrid readings taken on each 2x2 filter section will
approximate the same as 16 readings.
Additional independent testing on the Envirco Mac 10
4x4 shows that using two-2x4 hoods simultaneously give
airflow data (cfm) with 5 percent of a duct traverse using 10
diameters of straight duct upstream of the fan intake.