Mac 10, Ledc, 4x4 fan filter unit – Envirco MAC 10 LE-DC User Manual
Page 11
MAC 10
®
LEDC
4x4 Fan Filter Unit
11
Innovators in Clean Air Technology | www.envirco.com | Operation & Maintenance
I n s t a l l a t i o n & S e r v i c e M a n u a l
COMMUNICATION SPECIFICATIONS
Overview:
•
MODBUS RTU protocol over RS485 (serial)
•
9600 baud rate, word length is 8, parity is none(n), stop bits=1
•
255 unique address values selectable by S2 switch settings
(recommended network node capacity 200 nodes)
•
Slew rate limited transceivers for improved network performance MODBUS Register Summary Table
• DO NOT USE CROSSOVER CABLES. THIS MAY DAMAGE THE CONTROL CARD OR RENDER IT NON-OPERATIONAL.
MODBUS Register Specifications:
Register
Name
R/W Values & Defaults
Units
Origin
Comments
1
RUN/STOP
RW
0,1
1
RAM
power up from REG 14
2
DEMAND
RW
0-100
%
RAM
power up from REG 10
6
SPEED
R
0,5-2000
RPM
LIVE
7
ANA1
R
0-1000
-
LIVE
Onboard Pot 0-1000=0-100%
9
STATUS
R
see detail
-
LIVE
10
DEFAULT SPEED
RW
0-100
50
EEPROM
applies to network only
12
CURRENT SPEED
R
0-100
-
LIVE
14
DEFAULT RUN/STOP
RW
0,1
1
EEPROM
applies in network mode only
24
ANA2
R
0-1000
-
LIVE
0-10V input 0-1000=0-10VDC
To reset non-volatile registers to factory default values, write 170 (AA hex) to Register 14, and then cycle power.
Note: Register 24 may be read in network mode to determine the value of 0-10VDC signal that may be connected.
For example, a pressure transducer may be connected to indicate unit interal static pressure.