Maintenance, Lubrication, Cleaning coils – Carrier LIGHT COMMERCIAL CONDENSING UNITS 38HDL018-060 User Manual
Page 10: Table 7 — recommended compressor oils

MAINTENANCE
Before performing recommended maintenance, be sure
unit main power is off. Failure to do so may result in
electrical shock or injury from rotating fan blades.
Lubrication
FAN-MOTOR BEARINGS — Oiling holes are provided at
each end of the condenser-fan motor. Remove fan motor and
lubricate motor with 32 drops (16 drops per hole) of SAE-10
(Society of Automotive Engineers) non-detergent oil at in-
tervals described below:
• Annually, when environment is very dirty, ambient tem-
perature is higher than 105 F (40 C), and average unit op-
erating time exceeds 15 hours a day, or
• Every three years, when environment is reasonably clean,
ambient temperature is less than 105 F (40 C), and unit
operating time averages 8 to 15 hours per day, or
• Every 5 years when environment is clean, ambient tem-
perature is less than 105 F (40 C), and unit operating time
averages less than 8 hours per day.
COMPRESSOR — Compressor contains factory oil charges;
replace oil when lost. See Tables 1A and 1B for oil recharge
and refer to Carrier Standard Service Techniques Manual,
Chapter 1, pages 1 to 21 for oil recharging procedure. See
Table 7 for recommended compressor oils.
Cleaning Coils
— Coil should be washed out with wa-
ter or blown out with compressed air. Note that the blow-
thru design causes dirt and debris to build up on the inside
of the coils.
Clean coil annually or as required by location and outdoor
air conditions. Inspect coil monthly and clean as required.
Fins are NOT continuous through coil sections. Dirt and de-
bris may pass through the first section, become trapped be-
tween the rows of fins, and restrict condenser airflow. Use a
flashlight to determine if dirt or debris has collected between
coil sections. Clean coil as follows:
1. Turn off unit power.
2. Use a garden hose or other suitable equipment to flush
coil from the outside to remove dirt. Be sure to flush all
dirt and debris from drain holes in the base of unit. Fan
motors are waterproof.
Table 6A — Required Liquid Line Temperature (F) — English (At Service Valve)
REQUIRED
SUBCOOLING (F)
LIQUID PRESSURE AT SERVICE VALVE (PSIG)
134
141
148
156
163
171
179
187
196
205
214
223
233
243
253
264
274
285
297
309
321
331
346
359
0
76
79
82
85
88
91
94
97
100
103
106
109
112
115
118
121
124
127
130
133
136
139
142
145
5
71
74
77
80
83
86
89
92
95
98
101
104
107
110
113
116
119
122
125
128
131
134
137
140
10
66
69
72
75
78
81
84
87
90
93
96
99
102
105
108
111
117
120
123
126
129
129
132
135
15
61
64
67
70
73
76
79
82
85
88
91
94
97
100
103
106
109
112
115
118
121
124
127
130
20
56
59
62
65
68
71
74
77
80
83
86
89
92
95
98
101
104
107
110
113
116
119
122
125
25
51
54
57
60
63
66
69
72
75
78
81
84
87
90
93
96
99
102
105
108
111
114
117
120
Table 6B — Required Liquid Line Temperature (C) — SI (At Service Valve)
REQUIRED
SUBCOOLING (C)
LIQUID PRESSURE AT SERVICE VALVE (PSIG)
911
969
1030
1061
1121
1186
1219
1286
1360
1397
1471
1547
1588
1671
1755
1800
1885
1976
2026
2125
2222
2264
2379
2475
0
24
26
28
29
31
33
34
36
38
39
41
43
44
46
48
49
51
53
54
56
58
59
61
63
2
22
24
26
27
29
31
32
34
36
37
39
41
42
44
46
47
49
51
52
54
56
57
59
61
4
20
22
24
25
27
29
30
32
34
35
37
39
40
42
44
45
47
49
50
52
54
55
57
59
6
18
20
22
23
25
27
28
30
32
33
35
37
38
40
42
43
45
47
48
50
52
53
55
57
8
16
18
20
21
23
25
26
28
30
31
33
35
36
38
40
41
43
45
46
48
50
51
53
55
10
14
16
18
19
21
23
24
26
28
29
31
33
34
36
38
39
41
43
44
46
48
49
51
53
12
12
14
16
17
19
21
22
24
26
27
29
31
32
34
36
37
39
41
42
44
46
47
49
51
14
10
12
14
15
17
19
20
22
24
25
27
29
30
32
34
35
37
39
40
42
44
45
47
49
Table 7 — Recommended Compressor Oils
RECOMMENDED
OIL
UNIT 38HDL
018
024
030
036
048
060
3GS
Calumet RO-15
Sontex 200LT
•
•
•
•
•
•
•
10