beautypg.com

Venting (cont’d), Gas piping, Awarning – Kenmore 153.33459 User Manual

Page 14: Gas piping -15, Installation instructions (contad)

Attention! The text in this document has been recognized automatically. To view the original document, you can use the "Original mode".

background image

Installation Instructions (contad)

Venting (cont’d)

All vent gases must be completely vented to the outdoors of the

structure (dwelling). Install only the draft hood provided with

the new water heater and no other draft hood.

Vent pipes must be secured at each joint with sheet metal screws.

TO

CHIMNEY

MIN. /4 INCH

RISE PER LINEAR

FOOT

3

VENT PIPE INSTALtATION

Gas Piping

AWARNING

Make sure the gas supplied is die same type listed on the
model rating plate. inlet gas pressure must not exceed

14 inches water column

'A

pound per square inch (3.5kPa).

The minimum inlet gas pressure listed m the modd rating

plate is for the purpose of input adjustment.

AWARNING__________________ ^

If the gas control valve is subjected to pressures exceeding

A

pound per square inch (3.5k№), the damage to the gas con­
trol valve could result in a fire or explosion

leaking gas.

There must be a minimum of 6" clearance between single wall

vent pipe and any combustible material. Fill and seal any clear­

ance between single wall vent pipe and combustible material

with mortar mix, cement, or other noncombustible substance.

For other than single wall, follow vent pipe manufacturer’s clear­

ance specifications. To insure a tight fit of the vent pipe in a

brick chimney, seal around the vent pipe with mortar mix

cement.

AWARNING

Failure to have required clearances between vent piping and
combustible material will result in a fire hazard.

AWARNING

Be sure vent pipe is properly connected to prévoit escape of
dangerous flue gases which could cause deadly asphyxiation.

AWARNING

Chemical vapor corrosion of the flue and vent system may
occur if air for combustion contains certain chemical vapors.
Spray can propellants, cleaning solvents, refrigerator and air
conditioner refrigerants, swimming pool chemicals, calcium
and sodium chloride, waxes, bleach, and process chemicals are
typical compounds which are potentially corrosive.

AWARNING__________________ ^

If the main gas line shutoff serving all gas appliances is used,

also turn “OFF” the gas at each appliance. Leave all gas appli­
ances shut off until the water heater installation is comfdete.

A gas line of sufficient size must be run to the water heater.

Consult the latest edition of National Fuel Gas Code ANSI

Z223.1, also referred to as NFPA54 and the gas company concern­

ing pipe size.

There must be:

• A teadily accessible manual shut off valve in the gas supply line

serving the water heater, and

• A drip leg (sediment trap) ahead of the gas control valve to help

prevent dirt and foreign materials from entering the gas control

valve.

• A flexible gas connector or a ground joint union between the

shutoff valve and control valve to permit servicing of the unit.

Be sure to check all the gas piping for leaks before lighting the

water heater. Use a soapy water solution, not a match or open

flame. Rinse olFsoapy solution and wipe dry.

Standard Models are for installation up to 3,300 feet above sea

level.
High Altitude Models are for installation from 3,300 to 3,500

feet above sea level.

If a standard model is installed above 3,300 feet or a high altitude

model is installed above 5,500 feet, the input rating must be

reduced at the rate of 4 percent for each 1,000 feet above sea level.

Contact your local Sears Service Center or gas utility for further

information.

AWARNING

The appliance and its gas connection must be leak tested

before placing the appliance in operation.

14