TROUBLESHOOTING CHART (CONTINUED)

PROBLEM

POSSIBLE CAUSE(S)

CORRECTIVE ACTION

SLOW HOT WATER

1.

Insufficient combustion air

1.

Provide ventilation to water heater. Check flue

RECOVERY

2.

Water heater flue or vent system

blocked

2.

way, flue baffle, and burner

Clean flue, locate source and correct

3.

Low gas pressure

3.

Check with gas utility company

4.

Improper calibration

4.

Replace thermostat

5.

Base-Ring Filter blocked with lint/dust5.

Clean filter. See “External Cleaning &

Inspection of the Base-Ring Filter” section.

6.

FVIR Flame Arrestor blocked with lint/6.

Clean filter. See “Cleaning the Combustion

dust.

Chamber and Flame-Arrestor” section.

DRIP FROM RELIEF VALVE

1.

Excessive water pressure

1.

Use a pressure reducing valve and relief

2.

Heater stacking

valve

3.

Closed water system

2.

Lower the thermostat setting

3.

See “Closed System/Thermal Expansion”

THERMOSTAT FAILS TO 1. Thermostat not functioning properly

1.

Replace thermostat

SHUT-OFF

2.

Improper calibration

2.

Replace thermostat

COMBUSTION ODORS

1.

Insufficient combustion air

1.

Provide ventilation to water heater. Check flue

way, flue baffle, and burner

2.

Water heater flue or vent system

blocked

2.

Clean, locate source and correct

3.

Heater installed in a confined area

3.

Provide fresh air ventilation

4.

Base-Ring Filter blocked with lint/dust4.

Clean filter. See “External Cleaning &

Inspection of the Base-Ring Filter” section.

5.

FVIR Flame Arrestor blocked with lint/5.

Clean filter. See “Cleaning the Combustion

dust.

Chamber and Flame-Arrestor” section.

SMOKING AND CARBON 1.

Insufficient combustion air

1.

Provide ventilation to water heater. Check flue

FORMATION (SOOTING)

2.

Low gas pressure

2.

way, flue baffle, burner

Check with gas utility company

3.

Water heater flue or vent system

blocked

3.

Clean, locate source and correct

4.

Thermostat not functioning properly

4.

Replace thermostat

5.

Heater installed in a confined area

5.

Provide fresh air ventilation

6.

Burner flame yellow-lazy

6.

See “Burner Flame Yellow-Lazy”

7.

Base-Ring Filter blocked with lint/dust7.

Clean filter. See “External Cleaning &

Inspection of the Base-Ring Filter” section.

8.

FVIR Flame Arrestor blocked with lint/8.

Clean filter. See “Cleaning the Combustion

dust.

Chamber and Flame-Arrestor” section.

CONDENSATION

1. Temperature setting too low

1.

Increase the temperature setting. Refer to the

“Condensation” sub-section of this manual’s

Troubleshooting Guide.

BURNER FLAME FLOATS 1.

Orifice too large

1.

Replace with correct orifice

AND LIFTS OFF PORTS

2.

High gas pressure

2.

Check with gas utility company

3.

Water heater flue or vent system

blocked

3.

Clean flue and burner-locate source and correct

4.

Cold drafts

4.

Locate source and correct

BURNER FLAME TOO HIGH

1.

Orifice too large

1.

Replace with correct orifice

FLAME BURNS AT ORIFICE

1. Thermostat not functioning properly

1.

Replace thermostat

2.

Low gas pressure

2.

Check with gas utility company

PILOT FLAME

1.

Pilot line or orifice clogged

1.

Clean, locate source and correct

TOO SMALL

2.

Low gas pressure

2.

Check with gas utility company

38